Underfloor Heating Calculator

List the rooms with their area and heat loss, pick the floor covering and pipe spacing, and set the flow temperature. The tool gives the output per square metre, floor surface temperature against the comfort limit, return temperature, downward loss, pipe length, number of loops, flow per loop, pressure drop and a manifold schedule.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Add the rooms

    Enter each room's size and heat load from a heat loss calculation, and its design temperature.

  2. 2
    Describe the floor

    Choose the floor covering, pipe spacing, screed depth and the insulation below the pipes.

  3. 3
    Set the flow temperature

    Type the flow temperature and the design spread between flow and return.

  4. 4
    Check each room

    Read the output needed, floor surface temperature, return temperature and any warnings.

  5. 5
    Plan the loops

    See pipe length, loops, flow per loop and pressure drop, and change the spacing where needed.

  6. 6
    Print the schedule

    Open the manifold tab for the port count and totals, then print or export the loop schedule.

About this tool

Wet underfloor heating is a large, low-temperature radiator under the floor. Its output depends on how warm the water is, how closely the pipes are laid, how thick and conductive the screed is above them and how much the floor covering resists heat. Design it badly and a room with thick carpet never reaches temperature, or a bathroom floor gets uncomfortably hot. This calculator uses the characteristic for pipes embedded in screed (type A) from EN 1264-2, which expresses the output as an equivalent heat transfer coefficient multiplied by the logarithmic mean temperature difference between water and room. For each room you enter the size, the heat load from your heat loss calculation, the room temperature, the temperature below the floor, the covering and the pipe spacing. The tool works out what output the room needs, what the floor can deliver at the chosen flow temperature, the return temperature that results, the floor surface temperature and whether it stays under the limit of 29 °C in occupied areas, 33 °C in bathrooms or 35 °C in edge zones, as EN 1264 sets out.

Loops and the manifold

Pipe length is the heated area divided by the spacing plus the flow and return leaders to the manifold. When the total is longer than the maximum loop length you set, often 100 m for 16 mm pipe, the room is split into equal loops, each on its own manifold port. For each loop you get the water flow in litres per minute for balancing the flow meters, the velocity and the pressure drop with an allowance for bends. The schedule tab totals the ports, pipe, heat and flow and finds the index loop for the pump, as well as the lowest flow temperature that lets every room reach its load.

Coefficients

The type A characteristic uses a base coefficient and factors for spacing, screed cover and pipe diameter that depend on the covering resistance. We keep them on the third tab as editable example values, because they come from our reading of the standard and makers often publish certified output tables for their own systems. Check them before you rely on a design.

Limits

The tool is not a full EN 1264 design. It does not model edge zones separately, dry or timber floor systems, the effect of insulation edge strips or heat pump cycling, and it assumes the whole room area is heated. Heat loads must come from a proper heat loss calculation. Use the system maker's design software for the final layout.

Worked example

A living room of 6 m by 4.5 m loses 1500 W, has carpet and underlay with a resistance of 0.10 m²K/W and pipes at 150 mm centres in 45 mm of sand and cement screed, with the flow at 40 °C. The room needs 55.6 W/m². The equivalent coefficient is 3.43 W/(m²K), so the return comes back at 33.0 °C and the floor surface is about 25.3 °C, well under the 29 °C limit. With 4 m leaders the pipe is 188 m long, so the room gets two loops of about 94 m, each needing 2.0 L/min with a pressure drop of about 16 kPa. Across the three example rooms the lowest workable flow temperature is about 39.7 °C.

Quick facts

Frequently asked questions

What flow temperature does underfloor heating need?

Usually between 35 and 45 °C in screed systems. The tool shows the lowest flow temperature that meets the load in every room; lower is better for heat pumps and condensing boilers.

Which pipe spacing should I use?

Closer spacing gives more output at the same water temperature. The tool reports the widest standard spacing that still meets each room's load, so you can use 100 or 150 mm where the load is high and 200 mm or more elsewhere.

Does carpet stop underfloor heating working?

It reduces the output. EN 1264 limits the covering resistance to 0.15 m²K/W; a thick carpet with heavy underlay can exceed that, so check the tog value with the carpet supplier and pick a thinner underlay.

How long can one loop be?

Many makers allow about 100 m for 16 mm pipe and 120 m for 20 mm pipe so that the pressure drop and flow stay reasonable. Type your maker's limit; the tool splits longer runs into equal loops.

Why is the floor temperature limited?

Floors warmer than about 29 °C feel uncomfortable underfoot and dry the air. EN 1264 allows 33 °C in bathrooms and 35 °C in edge zones near windows where people do not stand for long.

What is the downward loss?

Some heat goes down into the slab or the room below. Better insulation under the pipes cuts it; the tool shows it per square metre and adds it to the heat the water must deliver.