How to Design Underfloor Heating: Output, Spacing and Loops
Find the output each room needs, the pipe spacing and flow temperature that deliver it, the floor temperature limit and how many loops to lay.

How to Design Underfloor Heating: Output, Spacing and Loops
Underfloor heating works best when it is designed rather than guessed. Lay the pipes too far apart under a thick carpet and the room never warms up; run the water too hot and the floor becomes uncomfortable while a heat pump loses efficiency. The design follows a clear sequence: work out what each room needs, check what the floor can give at a chosen water temperature, and then plan the pipe and loops.
Start from the heat loss
Every room has a design heat loss in watts at the coldest expected weather, from a proper heat loss calculation. Divide it by the heated floor area to get the output the floor must deliver in watts per square metre. A well insulated living room might need 40 to 60 W/m²; an old room with large windows may need more than the floor can provide.
The comfort limit
Floor output is limited by how warm the surface can be. EN 1264 links output to the floor surface temperature with a simple curve: q = 8.92 × (floor temperature − room temperature)^1.1. In occupied areas the floor should not exceed 29 °C, which at 20 °C room temperature caps output at about 100 W/m². Bathrooms may go to 33 °C and edge zones near windows to 35 °C. If a room needs more, add another emitter.
What the floor can deliver
For pipes laid in screed, EN 1264-2 expresses the output as an equivalent heat transfer coefficient multiplied by the logarithmic mean temperature difference between the water and the room. The coefficient depends on:
- Pipe spacing: closer pipes give more output at the same water temperature.
- Screed depth and conductivity above the pipe.
- Floor covering: tiles barely resist heat, carpet and thick underlay resist a lot. The standard limits the covering to a resistance of 0.15 m²K/W.
- Pipe diameter, which has a small effect.
Choosing the flow temperature
Lower flow temperatures save energy, especially with heat pumps. The design flow temperature is set by the most demanding room: the one with the highest output per square metre relative to its spacing and covering. Other rooms then run with a larger difference between flow and return, which the manifold valves balance.
A worked example
A 6 m by 4.5 m living room loses 1500 W, so it needs 55.6 W/m². It has carpet and underlay at 0.10 m²K/W, pipes at 150 mm in 45 mm of screed, and water at 40 °C. The equivalent coefficient comes out at about 3.43 W/(m²K). To deliver 55.6 W/m² the return must be about 33 °C, and the floor surface runs at about 25.3 °C, well below 29 °C. The room is fine at this flow temperature.
Pipe length and loops
Pipe length is the area divided by the spacing, plus the flow and return leaders to the manifold. At 150 mm the living room needs 27 / 0.15 = 180 m, plus 8 m of leaders, 188 m in total. Most makers limit a 16 mm loop to about 100 m so that the pump can push enough water through it, so this room gets two loops of about 94 m. Each loop needs about 2 litres per minute, with a pressure drop of about 16 kPa. Count the loops across all rooms and you have the number of manifold ports; the longest or most resistant loop, the index loop, sets the pump head.
Practical tips
- Use closer spacing near large windows and in rooms with high loads; 200 mm or more is fine for low-load rooms.
- Keep the covering resistance low: ask for tog values and choose thin underlays.
- Insulate well under the pipes to cut downward losses, especially on ground floors.
- Balance each loop to its design flow with the manifold flow meters.
Using the calculator
The Underfloor Heating Calculator runs this sequence for several rooms. Enter each room's size, heat load, temperatures, covering and spacing, and the system's flow temperature, screed and pipe details. It shows the needed output, the floor surface temperature against the limit, the return temperature, downward loss, pipe length, loops, flow and pressure drop per loop, and the widest spacing that would still work. The manifold tab totals ports, pipe and flow and gives the lowest flow temperature that suits every room, ready to print as a loop schedule. The EN 1264-2 coefficients are editable example values, so check them against the standard or your system maker's certified tables before final design.