Star-Delta Starter Calculator

Type a motor's kW, voltage, efficiency and power factor to size the three contactors and the overload relay, check the start, and build a panel schedule.

ทำงานในเบราว์เซอร์ของคุณ ไฟล์ไม่ออกจากอุปกรณ์ ดูวิธีตรวจสอบ

…

วิธีทำ

  1. 1
    Enter the nameplate

    Type tag, kW, line voltage, efficiency, power factor and rated speed.

  2. 2
    Add starting data

    Enter locked-rotor current, starting torque, load torque and total inertia.

  3. 3
    Place the overload

    Choose whether the overload relay is in the winding circuit or the supply line.

  4. 4
    Read the sizes

    Note the KM1, KM2, KM3 and overload tiles, and check the star torque warning.

  5. 5
    Set the timer

    Use the timer guide and the estimated run-up time.

  6. 6
    Build the schedule

    Press Add to panel schedule for each motor, then Report or CSV.

เกี่ยวกับเครื่องมือนี้

A star-delta starter is the classic way to start a three-phase induction motor with less inrush than direct-on-line. The motor windings are first connected in star, so each winding sees the line voltage divided by √3; current and torque both fall to one third of their direct-on-line values. Once the motor has run up, a timer drops the star contactor and closes the delta contactor so each winding gets full voltage. Because the main and delta contactors carry only the winding current, which is 58 % of the line current, the starter uses three smaller contactors rather than one large one. Getting the sizes wrong is a common panel-building mistake: an overload relay set to the full line current never trips when it sits in the winding circuit, and a motor whose load torque is too high will stall in star and then hit the supply with a big current spike when it changes over. This calculator takes the motor nameplate, works out full-load and winding currents, picks contactors from common AC-3 frame sizes, places the overload range, compares the star starting torque with the load and estimates the run-up time for setting the timer.

Currents and contactors

The full-load line current is P / (√3 × U × η × cos φ). In delta each winding carries that current divided by √3. The main contactor KM1 and the delta contactor KM3 are in the winding circuit, so manufacturers size each at 0.58 times the full-load current. The star contactor KM2 only carries current during the start, at one third of the line current, so 0.33 times is used. The calculator rounds each value up to the next common AC-3 frame size; always confirm the exact part in the maker's table for your voltage, because AC-3 ratings fall at higher voltages.

Overload relay position

Most starters put the overload relay after KM1, in series with the windings, where it sees 0.58 times the full-load current. If yours is in the supply line ahead of the starter, select that option and the setting becomes the full line current. The tile shows a relay range that covers the setting.

Will it start in star?

Star torque is one third of the motor's locked-rotor torque. If the load needs more than that at low speed, as a loaded conveyor or a compressor without unloading can, the motor will not accelerate and the changeover becomes a near direct-on-line start. The tile compares the two and warns you. With the total inertia of motor and load, the calculator also estimates the run-up time to about 85 % speed, which is when the change to delta should happen.

Wiring and schedule

The Wiring tab draws the power circuit with terminal markings U1, V1, W1 and U2, V2, W2. Add each motor to the panel schedule, then print the schedule or download it as CSV for the panel builder.

Limits

These figures do not replace a licensed engineer's design. Timer estimates use a simple average-torque model; measure the real run-up and adjust. Closed-transition starters, two-speed motors and soft starters are not covered.

ตัวอย่างพร้อมวิธีทำ

A 22 kW pump motor at 400 V has η 0.92 and cos φ 0.86. Full-load current is 22,000 / (1.732 × 400 × 0.92 × 0.86) = 40.1 A, and the winding current in delta is 23.2 A. KM1 and KM3 each need 0.58 × 40.1 = 23.3 A, so 25 A AC-3 contactors; KM2 needs 13.2 A, so 18 A. The overload relay in the winding circuit is set to 23.2 A on a 17 to 25 A relay. With a locked-rotor current of 7 times, the start current falls from 281 A to 94 A. Star torque is 105 N·m against 43 N·m of load, and with 1.5 kg·m² of inertia the run-up takes about 3.8 s, so the timer is set near 5 s.

สรุปสั้น ๆ

คำถามที่พบบ่อย

Why are the main and delta contactors only 58 % of the motor current?

In a star-delta starter they switch the winding current, not the line current. In delta the winding current is the line current divided by √3, which is 0.577 times.

What voltage must the motor be rated for?

It must run in delta at your supply voltage, so on a 400 V system you need a 400 V delta / 690 V star motor. A 230/400 V motor would be over-voltaged in delta.

How do I set the star-delta timer?

Set it to the time the motor takes to reach about 80 to 90 % of rated speed in star, typically 5 to 15 seconds for pumps and fans. Watch the current fall during the start; change over just after it levels off.

Why does my starter trip or spike when it switches to delta?

Usually the timer is too short or the load torque is too high for star starting, so the motor changes over at low speed. The other cause is changing over too fast without the short open pause, which lets the star contactor arc.

Can I use the tool for 60 Hz or 480 V systems?

Yes. Enter your line voltage and the nameplate values; the formulas do not depend on frequency. Use the maker's AC-3 table for the contactor ratings at that voltage.

Does the schedule stay after I close the page?

Yes, it is saved in this browser. Use the JSON button for a backup you can open on another device.