Control Valve Cv Sizing Calculator
Enter the minimum, normal and maximum flow cases for liquid, gas or steam with the inlet and outlet pressures. The tool works out the required Kv and Cv with the IEC 60534-2-1 equations, flags choked flow, flashing and cavitation, includes reducers, picks a valve from an editable catalogue and shows the travel for every case on the characteristic.
Runs in your browser. Your files never leave your device. See how to check
…
How to do it
- 1Choose the fluid
Pick liquid, gas or steam and the flow and pressure units you work in.
- 2Enter the cases
Type the minimum, normal and maximum flow with the inlet and outlet pressures and temperature.
- 3Add fluid properties
For liquids enter density and vapour pressure, for gases molar mass, Z and the heat ratio.
- 4Set valve factors
Type FL and xT from the maker's data, and the reducer sizes if the valve is smaller than the line.
- 5Choose the valve
Read Kv and Cv per case, then pick a valve and check the travel on the characteristic chart.
- 6Print the sheet
Print the sizing sheet with every case or export it as CSV for the valve data sheet.
About this tool
The flow coefficient of a valve says how much it passes for a given pressure drop. Kv is the flow of water in cubic metres per hour with a pressure drop of 1 bar, and Cv is the flow in US gallons per minute with a drop of 1 psi; Cv is about 1.156 times Kv. Sizing a control valve means finding the coefficient that each operating case needs and then choosing a valve whose rated coefficient puts those cases in the useful middle of its travel. This calculator uses the equations of IEC 60534-2-1, which are the same as ANSI/ISA-75.01.01, for turbulent flow of incompressible and compressible fluids. For liquids it computes the liquid critical pressure ratio factor from the vapour pressure and critical pressure, the pressure drop at which flow chokes and the cavitation index, and tells you when the outlet is below the vapour pressure so the liquid flashes. For gases and vapours it uses the pressure drop ratio, the specific heat ratio factor and the expansion factor, which bottoms out at two thirds when the flow is choked. For steam it takes the inlet density from IAPWS-IF97, so you only enter the pressure and temperature.
Several cases and the valve choice
A control valve has to work at the lowest and the highest flow as well as at the design point. List all three cases, and the tool reports the Kv and Cv for each, picks the smallest catalogue valves that take the largest case at or below 85 percent travel and draws the inherent characteristic, equal percentage, linear or quick opening, with each case marked on it. Most engineers aim for roughly 20 to 80 percent travel across the cases.
Reducers
If the valve is smaller than the pipe, the reducers add losses. Type the valve and pipe inside diameters and the tool includes the piping geometry factor Fp, and for liquids the combined factor FLP, by iteration as the standard describes.
Checked against the standard
The liquid and gas equations reproduce the worked examples in the annex of IEC 60534-2-1: 360 m³/h of water at 90 °C from 680 to 220 kPa needs a Kv of about 165, and 3800 m³/h of carbon dioxide at 160 °C from 680 to 310 kPa needs about 62.7.
Limits
The valve catalogue is an example list of generic globe and segmented ball valves with typical FL and xT factors; real valves differ and the maker's sizing data must be used. The tool does not apply the Reynolds number factor for viscous or laminar flow, two-phase flow, noise prediction, or trim and actuator selection.
Worked example
A hot water control valve must pass 360 m³/h of water at 90 °C, with a density of 965.4 kg/m³ and a vapour pressure of 70.1 kPa, from 680 kPa to 220 kPa absolute. With FL = 0.9 the choked pressure drop is 497 kPa, so the flow is not choked and Kv = 164.9 (Cv 190.7). The normal case of 250 m³/h from 700 to 420 kPa needs Kv 146.8 and the minimum case of 60 m³/h from 720 to 620 kPa needs Kv 59.0. In a DN150 equal percentage globe valve with Kvs 360 and rangeability 50 the three cases sit at about 80, 77 and 54 percent travel.
Quick facts
- Category: Engineering & Construction
- Works in your browser, no sign-up, no upload.
- Your input stays on your device.
- Available in English.
- Content last reviewed:
- Official source: IEC 60534-2-1:2011 / ANSI/ISA-75.01.01 flow equations for sizing control valves
Frequently asked questions
What is the difference between Cv and Kv?
Both measure valve capacity. Kv is in m³/h of water at 1 bar drop and Cv in US gallons per minute at 1 psi drop. Cv = 1.156 × Kv and Kv = 0.865 × Cv.
What does choked flow mean?
Beyond a certain pressure drop the flow stops increasing. In liquids this happens when vapour bubbles form in the valve; in gases when the flow reaches sonic speed. The tool sizes with the choked pressure drop and warns you.
How do I know if a valve will cavitate?
Cavitation starts before full choking. The tool shows the cavitation index σ = (p1 − pv) / (p1 − p2); values below about 2 need a check against the valve maker's incipient cavitation figure and possibly an anti-cavitation trim.
Which FL and xT should I use?
They depend on the valve style and trim. Globe valves are often around FL 0.9 and xT 0.7; ball and butterfly valves are lower. Use the values from the maker's data sheet for the valve you plan to buy.
Can it size steam valves?
Yes. Choose steam, enter the flow in kg/h or lb/h with the inlet pressure and temperature, and the tool takes the steam density from IAPWS-IF97 and uses the compressible flow equation.
Why size with three cases?
A valve sized only for the maximum may be almost closed at the minimum flow, where control becomes poor. Checking the travel at minimum, normal and maximum shows whether one valve covers the whole range.