How to Size a Control Valve: Cv, Kv, Choked Flow and Travel

Calculate the Cv or Kv a control valve needs for liquid, gas or steam, spot choked flow and cavitation, and pick a valve with good travel.

Saizul Amin
Saizul Amin19 Nov 2026 · 4 min read
How to Size a Control Valve: Cv, Kv, Choked Flow and Travel

How to Size a Control Valve: Cv, Kv, Choked Flow and Travel

An oversized control valve is one of the most common reasons a loop hunts. It spends its life nearly closed, where a tiny movement makes a big change in flow, and the controller can never settle. An undersized valve simply cannot pass the maximum flow. Sizing is about finding the flow coefficient each operating case needs and choosing a valve that puts those cases in the middle of its travel.

Cv and Kv

The flow coefficient describes how much a valve passes for a given pressure drop. Kv is the flow of water in cubic metres per hour with a 1 bar drop; Cv is the flow of water in US gallons per minute with a 1 psi drop. They are linked by Cv = 1.156 × Kv. Every valve has a rated coefficient at full travel, often written Kvs or rated Cv.

Liquids

For a liquid in turbulent flow the basic relation is Kv = Q × √((ρ/1000) / Δp), with Q in m³/h and Δp in bar. More pressure drop gives more flow, but only up to a point. As the drop increases, the pressure at the narrowest point inside the valve falls below the vapour pressure, bubbles form and the flow chokes. IEC 60534-2-1 gives the limiting drop as FL² × (p1 − FF × pv), where FL is the valve's liquid pressure recovery factor and FF depends on the ratio of vapour pressure to critical pressure. Beyond that, extra drop adds no flow and the collapsing bubbles cause cavitation damage and noise. If the outlet pressure is below the vapour pressure, the liquid flashes, which needs different trim.

The standard's own example: 360 m³/h of water at 90 °C, density 965.4 kg/m³ and vapour pressure 70.1 kPa, from 680 to 220 kPa absolute, with FL = 0.9. The choked drop is about 497 kPa, so 460 kPa is not choked, and Kv is about 165.

Gases and steam

Gases expand as they pass through the valve, so the equation includes an expansion factor Y = 1 − x / (3 × Fγ × xT), where x is the pressure drop divided by the inlet pressure, Fγ is the specific heat ratio divided by 1.4, and xT is a valve factor. When x reaches Fγ × xT the flow chokes and Y bottoms out at two thirds. The standard's gas example, 3800 normal m³/h of carbon dioxide at 160 °C from 680 to 310 kPa, needs a Kv of about 62.7.

Steam uses the same compressible equation with mass flow and the inlet density, which you take from steam tables.

Minimum, normal and maximum

A valve has to control across its whole range, not just at the design point. List the cases, typically minimum, normal and maximum flow, each with its own pressures; the pressure drop across the valve often grows at low flow because the pump runs back up its curve. In the water example the normal case of 250 m³/h needs Kv 146.8 and the minimum of 60 m³/h needs Kv 59.0.

Characteristic and travel

The inherent characteristic links travel to flow coefficient. In an equal percentage valve each step of travel changes the flow by the same percentage of its current value; in a linear valve flow is proportional to travel. Equal percentage suits most process loops where the pressure drop across the valve falls as flow rises.

In a DN150 equal percentage globe valve with Kvs 360 and a rangeability of 50, the three water cases sit at about 80, 77 and 54 percent travel. A common aim is roughly 20 to 80 percent across all cases, so this valve is acceptable, if near the top for the maximum.

Using the calculator

The Control Valve Cv Sizing Calculator applies the IEC 60534-2-1 equations to as many cases as you list, for liquid, gas or steam, in kPa, bar or psia. It reports Kv and Cv per case, warns about choked flow, flashing and a low cavitation index, includes reducers through the piping geometry factor, and takes steam density from IAPWS-IF97. Pick a valve from the editable catalogue and the chart shows each case on its characteristic. The catalogue's FL and xT are typical figures; use the maker's data for the valve you buy.

Things the equations do not cover

Viscous liquids at low Reynolds numbers need a correction factor, two-phase flow needs special methods, and noise prediction is a separate part of the standard. Treat the result as the starting point for the valve maker's sizing, not the final selection.