Proctor Compaction Test: Finding Maximum Dry Density and Optimum Moisture

Calculate dry density for each Proctor point, fit the compaction curve, read MDD and OMC, draw zero air voids and check field compaction results.

Saizul Amin
Saizul Amin19 Nov 2026 · 4 min read
Proctor Compaction Test: Finding Maximum Dry Density and Optimum Moisture

Proctor Compaction Test: Finding Maximum Dry Density and Optimum Moisture

Every earthworks specification that asks for 95 percent compaction is referring to a laboratory number: the maximum dry density from a Proctor test. Getting that number right, and the optimum moisture content that goes with it, is the job of the free Proctor Compaction Test Calculator.

What the test measures

Soil is mixed at a range of moisture contents. At each one, it is compacted into a mould in layers with a fixed number of blows from a rammer dropped from a fixed height, then weighed. A moisture sample is taken from the compacted soil. Dry soil resists compaction, very wet soil has water filling the space soil could occupy, and somewhere between lies the moisture content that gives the densest packing.

Choosing the method

Standard and modified tests differ in effort. ASTM D698, BS 1377 light and IS 2720 Part 7 use roughly 600 kJ per cubic metre; ASTM D1557, BS heavy and IS Part 8 use about 2700. Pick a preset and the mould volume, rammer mass, drop, layers and blows fill in, with the compactive effort calculated from them. You can also enter a custom mould or rammer.

From masses to dry density

For each point, enter the mould mass, the mould with compacted soil, and the moisture content or the three tin weighings. Bulk density is the soil mass divided by the mould volume. Dry density removes the water: bulk density divided by one plus the moisture content as a decimal. Densities can be shown in g/cm³, kN/m³ or pounds per cubic foot.

Fitting the curve

The calculator fits a smooth curve through the points, either a parabola or a cubic, and finds its peak. The peak's height is the maximum dry density and its position is the optimum moisture content. The peak is only accepted inside the range you tested; if all your points are on the dry side, for example, you get a warning to add wetter points instead of a guess.

Zero air voids and saturation

The zero air voids line shows the dry density the soil would have if all the air were squeezed out and every pore were full of water. It depends on the specific gravity of the soil solids. No real test point can lie above it, so a point that does signals a weighing error or a wrong specific gravity. Lines at 90 and 80 percent saturation help you see how wet the points are, and each point lists its degree of saturation and air voids.

A worked example

A subgrade sample tested by ASTM D698 in a 944 cm³ mould gives five dry densities between 1.702 and 1.844 g/cm³ at moisture contents from 8.4 to 17.1 percent. The fitted curve peaks at a maximum dry density of 1.843 g/cm³ at 13.2 percent moisture. With a specific gravity of 2.68 the zero air voids density at that moisture is 1.978 g/cm³, comfortably above the curve. The compactive effort works out at 593 kJ/m³.

Oversize correction

Large stones are removed before the test because they do not fit the mould. If the field material contains them, the laboratory density must be corrected. ASTM D4718 does this from the percentage of oversize, its specific gravity and its moisture content. Turn the correction on and the corrected values replace the plain ones in the results.

Field compaction checks

On site, density tests give the dry density and moisture of each compacted layer. Enter them on the field tab with the required percentage. The calculator gives the relative compaction, the field density divided by the maximum dry density, and how far the moisture is from optimum, and marks each test pass or fail. In the example, 1.79 g/cm³ is 97.1 percent and passes, while 1.71 g/cm³ is 92.8 percent and fails a 95 percent requirement.

Report and caution

Print a report with the test details, point table, curve and field results, or export CSV and SVG. The fitted curve is a smoothing aid, not part of the standards, so check that it follows your points. Specifications, not the calculator, set the required percentage and moisture window. Have design-critical results checked by a qualified engineer.