Power Factor Correction Capacitor Calculator

Calculate the kvar and capacitance needed to raise the power factor of a three-phase load.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Step 1: Open Power Factor Correction Capacitor Calculator and add your input

    Type your numbers or text, add your file, or pick the options you need. Nothing is uploaded: everything stays in your browser.

  2. 2
    Step 2: What Power Factor Correction Capacitor Calculator does

    Calculate the kvar and capacitance needed to raise the power factor of a three-phase load.

  3. 3
    Step 3: Read the result and compare

    The result appears at once. Change one value to see how the answer moves, then keep the figure that fits your case.

  4. 4
    Step 4: Copy or save it

    Copy the result or download it. For an important decision, confirm it with the official source or an adviser.

About this tool

Enter the real power in kW, the present and the target power factor, the line voltage and the frequency. The calculator gives the capacitor bank size in kvar, the capacitance per phase for delta and star connections and the line current before and after.

Formulas

Required reactive power Qc = P × (tan φ₁ − tan φ₂), where φ = arccos(power factor). For a delta-connected bank each phase capacitance is C = Qc ÷ (3 ω V²) and for a star-connected bank C = Qc ÷ (ω V²), with ω = 2πf and V the line-to-line voltage.

Benefits

A higher power factor lowers the current and losses, and may avoid utility penalties. Line current = P ÷ (√3 V PF).

Cautions

Do not over-correct a motor load: a leading power factor and resonance with the supply can raise voltage. Use detuned reactors near harmonic sources.

Worked example

A 75 kW load at 0.78 raised to 0.95 at 400 V and 50 Hz needs 35.5 kvar, which is 235.5 µF per phase in delta. The line current falls from 138.8 A to 114 A.

Tips for best results

Check every box before you rely on a result, because one wrong digit changes the whole answer. Use the exact figures from your payslip, bill, certificate or contract, and keep a note of the date you calculated. Rates, thresholds and rules change from time to time, so for tax, fees and legal matters treat the output as an estimate and confirm with the official source named on this page. You can run as many scenarios as you like; nothing is saved or sent, and refreshing the page clears the boxes.

Quick facts

Embed this calculator on your site

Copy this code to show the calculator on your own page. A link back to shobfree.com is included.

Frequently asked questions

What target power factor?

0.95 or above avoids most utility penalties.

Delta or star?

Delta needs a third of the capacitance of star for the same kvar.

Can I over-correct?

Avoid it; a leading power factor can cause overvoltage.

Does it save energy?

It reduces cable and transformer losses, not the motor's own use.