PT100 RTD and Thermocouple Temperature Converter

Turn RTD resistance or thermocouple voltage into temperature and back, correct for lead wires and the cold junction, see tolerance classes and print lookup tables.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose the sensor

    Open the PT100 / PT1000 or Thermocouple tab and pick the sensor or type.

  2. 2
    Pick the direction

    Select resistance or millivolts to temperature, or the reverse.

  3. 3
    Enter the reading

    Type the measured value, plus lead resistance or cold-junction temperature.

  4. 4
    Read the result

    Check the temperature, the uncorrected value and the tolerance class.

  5. 5
    Make a table

    On Lookup table set range and step to see the curve and the values.

  6. 6
    Export

    Press CSV for a spreadsheet or Report for a printable sheet.

About this tool

Industrial temperature is mostly measured with two families of sensor. Platinum resistance thermometers such as the PT100 change resistance with temperature in a smooth, well-defined way and are used up to about 600 °C where accuracy matters. Thermocouples produce a small voltage from the junction of two different metals and cover a much wider range, up to 1,800 °C for the platinum types. When you commission or troubleshoot a loop you often have only a multimeter reading in ohms or millivolts and need the temperature it represents, or the reverse: you want to simulate a temperature with a decade box or a millivolt source. This converter uses the Callendar-Van Dusen equation and coefficients of IEC 60751 for platinum sensors, and the NIST ITS-90 reference polynomials that IEC 60584-1 adopts for the eight letter-designated thermocouple types. Inverse values are solved from the same functions, so a round trip returns the starting value. It also removes lead resistance for two-wire RTDs, adds the cold-junction voltage for thermocouples, shows the tolerance band for each class and builds tables you can print or download.

RTD conversion

For temperatures at or above 0 °C the resistance is R0 × (1 + A t + B t²). Below zero an extra term C (t − 100) t³ applies. A PT100 reads 100 Ω at 0 °C and 138.51 Ω at 100 °C; a PT1000 reads exactly ten times as much. Pick the sensor, choose the direction and type the value. If the sensor is wired with two wires, both lead resistances appear in series with the element and make the reading high; enter the resistance of each lead and the tool removes them. Three-wire and four-wire connections cancel the leads, so no correction is applied.

Thermocouple conversion with cold junction

A thermocouple measures the difference between the hot junction and the point where its wires meet copper, the cold junction. The meter therefore reads E(t) − E(t cold). To find t, the tool adds the voltage that corresponds to the cold-junction temperature, not the temperature itself, and then inverts the curve. The Without CJC tile shows how wrong the result would be if the cold junction were ignored. In the other direction it tells you what to dial on a millivolt calibrator for a given process temperature and terminal temperature.

Tolerances

IEC 60751 classes AA, A, B and C give the allowed deviation of an RTD as ± (a + b |t|). IEC 60584-1 classes 1 and 2 give the thermocouple limits, as a fixed value or a percentage of temperature, whichever is larger. The sensitivity tiles show how many ohms or microvolts one degree is worth at that point.

Lookup tables

The Lookup table tab draws the curve and lists values for any range and step for PT100, PT1000 or any thermocouple type, ready to print or export.

Limits

Not a substitute for a licensed engineer's or a calibration laboratory's judgement. Values are for sensors that follow the standard curves; individually calibrated sensors have their own coefficients. Type B is double-valued below about 50 °C, so the inverse starts there. Transmitter linearisation, drift and extension-cable errors are not included.

Worked example

A three-wire PT100 reads 119.40 Ω, so no lead correction is needed and t = 50.0 °C, with a class A tolerance of ± 0.25 °C. A two-wire sensor with 0.5 Ω per lead would show 120.40 Ω, which the tool corrects back by 1.0 Ω. A type K thermocouple gives 8.138 mV at the meter, and the terminals are at 25 °C. The cold-junction voltage is E(25) = 1.000 mV, so E(t) = 9.138 mV and the process temperature is about 225 °C. Ignoring the cold junction would have given about 200 °C, an error of 25 °C.

Quick facts

Frequently asked questions

What is the difference between PT100 and PT1000?

Both follow the same curve, but a PT1000 has ten times the resistance, 1,000 Ω at 0 °C. Its larger signal makes lead resistance and self-heating less important, which suits two-wire wiring and battery devices.

Why do I need cold-junction compensation?

The thermocouple voltage depends on the difference between the hot end and the terminals where it meets copper. Unless that terminal temperature is added back as a voltage, the reading is low by roughly the terminal temperature.

Which thermocouple types are supported?

Types K, J, T, E, N, R, S and B, each over its full IEC 60584-1 range, using the NIST ITS-90 reference functions.

How accurate are the conversions?

The forward functions are the standard reference equations, and the inverse is solved from them to within about 0.01 °C. The sensor tolerance class is usually a far larger uncertainty.

Can I use it to set up a calibrator?

Yes. Choose Temperature to millivolts, enter the process and terminal temperatures, and dial the meter voltage shown. For RTDs, the resistance value is what to set on a decade box.

Can I export a table?

Yes. Set the sensor, range and step on the Lookup table tab, then press CSV or Report.