MCB and Circuit Breaker Rating Calculator

List the appliances on a circuit and get the load current, the next standard breaker rating, the B, C or D curve and a copper wire that suits it.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose the rules

    Pick IEC MCB sizes for most of the world or NEC breakers for the USA and Canada, then single or three phase and the voltage.

  2. 2
    List the appliances

    Add each appliance with its watts, the number of them and its load type; the power factor fills in automatically.

  3. 3
    Set diversity and margin

    Lower diversity for loads that never run together and keep the 125 percent margin for loads that run for hours.

  4. 4
    Enter the cable run

    Type the one-way length from the board and the voltage drop you allow, often 3 percent.

  5. 5
    Read the breaker

    See the rating, trip curve, wire size and voltage drop, with a note when the wire is stepped up.

  6. 6
    Plan the board

    Add more circuits, read the main breaker size and print the schedule for your electrician.

About this tool

A miniature circuit breaker protects the wire behind the wall, not the appliance. If the breaker is too small it trips every time the kettle and the iron run together; if it is too large the cable can overheat before anything trips. Choosing it means three numbers in the right order: the current the circuit really draws, a breaker rating at or above that, and a wire that can carry at least the breaker rating. This calculator works them out from what people actually know, which is the watts printed on each appliance. You list fans, lights, a fridge, an air conditioner or a geyser, set the voltage and whether the supply is single or three phase, and the page turns watts into amps using the power factor of each load type. A diversity slider accounts for appliances that never run at the same moment, and a margin of 125 percent covers loads that stay on for hours. The result is the next standard MCB size, the trip curve suited to the loads, a copper conductor size and the voltage drop over your cable length. Several circuits can be planned on one board, with a main breaker for the total.

From watts to amps

On a single-phase supply the current is watts divided by volts and by the power factor. A 2,000 W kettle on 230 V draws 8.7 A because it is a pure resistance with a power factor of 1. A 1,000 W pump with a power factor of 0.8 draws 5.4 A, more than its watts suggest, because motors also draw reactive current. On three phase the current per line is watts divided by 1.732 times the line voltage times the power factor.

Which curve

Type B breakers trip instantly at three to five times their rating and suit heaters, lighting and electronics. Type C trips at five to ten times and rides through the starting surge of motors, compressors, pumps and air conditioners. Type D is for welders and transformers with very high inrush. The tool picks the highest curve that any load on the circuit needs.

Wire size and voltage drop

The IEC table assumes PVC-insulated copper in conduit in a wall at 30 °C, with two loaded conductors. The NEC table uses the familiar 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG limits. Long runs lose voltage, so the wire is stepped up until the drop is within your limit, often 3 percent for final circuits.

Limits

This is a planning aid, not a design approved under any wiring code. It does not apply grouping, insulation or high ambient temperature factors, does not check fault level or earth loop impedance, and does not replace an inspection. Local rules on minimum sizes for socket circuits, RCD protection and bathroom zones vary. A licensed electrician must check and carry out any fixed wiring work.

Worked example

A bedroom and living room circuit on 230 V single phase has three 75 W ceiling fans, eight 12 W LED lights, a 120 W television, a 200 W fridge and a 1,000 W iron: 1,641 W in total. The currents add up to 7.70 A. With a 125 percent margin the breaker must be at least 9.63 A, so the next standard size is a 10 A MCB, type C because the fans and fridge are motors. 1.5 mm² copper carries 17.5 A, and over a 15 m run the drop is about 1.5 percent. A 1,600 W split air conditioner on its own circuit draws 8.18 A and gets a 13 A type C breaker.

Quick facts

Frequently asked questions

What size MCB do I need for a 1.5 ton air conditioner?

A 1.5 ton inverter split AC usually draws 1,400 to 1,800 W. At 230 V and a power factor of 0.85 that is 7 to 9 A, so with a 125 percent margin a 13 A or 16 A type C MCB is typical, and many installers run 2.5 mm² wire to it. Check the rated current on the outdoor unit's label.

Why does my breaker trip when the kettle and iron run together?

A 2,000 W kettle and a 1,000 W iron draw about 13 A together on 230 V. On a 10 A breaker that overload trips it within minutes. Move one appliance to another circuit or have the circuit rewired for a larger breaker; never fit a larger breaker on the same thin wire.

What is the difference between B, C and D curve breakers?

They trip at different multiples of the rating during a sudden surge: B at 3 to 5 times, C at 5 to 10 times and D at 10 to 20 times. All three trip the same way on a slow overload. Use C for motors so the start-up surge does not cause nuisance trips.

What does diversity mean?

Diversity is the share of the connected load that is likely to run at once. In a living room the lights, fans and TV run together, but a kitchen rarely uses the kettle, microwave and toaster in the same minute. Lower it only where you are sure; keep 100 percent for a single large appliance.

Does the wire size depend on the breaker or on the load?

On the breaker. The cable must carry at least the breaker rating, because the breaker is what limits the current in a fault. That is why the calculator chooses the breaker first and then the smallest wire whose capacity is equal to or above it.

Should I add an RCCB or GFCI?

Yes for socket, bathroom, kitchen and outdoor circuits. An MCB protects against overload and short circuits, while a 30 mA residual current device trips on a small leak to earth that could pass through a person. Many wiring codes now require one.