Heat Exchanger LMTD and NTU Calculator

Enter hot and cold flows, specific heats, inlet temperatures and U to get the duty, outlet temperatures, LMTD and required area, or the effectiveness and duty of a given area.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose LMTD or NTU

    Design or rating.

  2. 2
    Pick the arrangement

    Counterflow, parallel or shell-and-tube.

  3. 3
    Enter flows and cp

    For both streams.

  4. 4
    Enter temperatures and U

    Inlets, and the hot outlet for LMTD.

  5. 5
    Read area or duty

    With outlet temperatures.

About this tool

Every heat exchanger calculation balances three things: the heat given up by the hot stream, the heat taken up by the cold stream and the heat that can pass through the walls, Q = U·A·ΔTlm. When all four temperatures are known, the log mean temperature difference (LMTD) method gives the area you need. When you have an exchanger and want to know what it will do, the effectiveness-NTU method is easier: it predicts the outlet temperatures from the inlet temperatures alone. This calculator does both for counterflow, parallel flow and shell-and-tube exchangers with one shell pass and an even number of tube passes, including the LMTD correction factor F. A what-if table shows how effectiveness and duty grow with area.

Who this is for

Process, HVAC and energy engineers, plant operators checking performance, and students of heat transfer.

LMTD method

1. Duty from the hot side: Q = ṁh·cph·(Thi − Tho). 2. Cold outlet from the energy balance: Tco = Tci + Q/(ṁc·cpc). 3. LMTD = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2), with ΔT at each end. 4. For shell-and-tube units, multiply by the correction factor F (from R and P). 5. Area A = Q/(U·F·LMTD). Keep F above about 0.75; lower values mean the temperature cross is too large for one shell pass.

Effectiveness-NTU method

- Heat capacity rates Ch = ṁh·cph and Cc = ṁc·cpc; Cmin is the smaller, Cr = Cmin/Cmax. - NTU = U·A/Cmin. - Effectiveness ε from the relation for the arrangement; Q = ε·Cmin·(Thi − Tci). Counterflow is always the most effective arrangement for a given NTU.

Typical overall U values (W/(m²·K))

| Service | U | |---|---| | Water to water, plate exchanger | 3,000-7,000 | | Water to water, shell and tube | 800-1,500 | | Steam to water | 1,000-4,000 | | Oil to water | 100-400 | | Gas to gas | 10-50 | | Air-cooled finned coil (bare area) | 300-500 |

Worked example (LMTD)

1 kg/s of water cooled from 90 to 50 °C by 1.5 kg/s of water entering at 15 °C: Q = 168 kW, the cold water leaves at 41.7 °C, LMTD = 41.3 K in counterflow, and with U = 1,500 W/(m²·K) the area is 2.71 m².

Worked example (NTU)

The same streams through 5 m²: NTU = 1.79, Cr = 0.67, ε = 71 % in counterflow, so Q = 223 kW and the outlets are 36.8 °C and 50.6 °C.

Fouling

Deposits on heat transfer surfaces add resistance. TEMA fouling factors range from 0.0001 m²·K/W for clean water to 0.0005 or more for river water and heavy oils. Include them when choosing U.

Limits

Constant properties and U, no phase change on both sides at once, no heat loss to surroundings. Crossflow arrangements are not included. This is not professional engineering advice.

Worked example

1 kg/s water from 90 to 50 °C against 1.5 kg/s at 15 °C needs 2.71 m² at U 1,500 (counterflow).

Quick facts

Frequently asked questions

When should I use LMTD or NTU?

LMTD when all temperatures are known (design); NTU when outlets are unknown (rating).

Why is counterflow better?

It keeps a larger temperature difference along the whole length.

What is the F factor?

A correction to LMTD for multi-pass shell-and-tube exchangers.

What is Cmin?

The smaller heat capacity rate ṁ·cp of the two streams.

How do I include fouling?

Add fouling resistances when calculating U.

Is my data stored?

No. Nothing is sent to a server.