Gas Pipe Sizing Calculator

Enter the appliance heat input, gas type, pipe length, fittings and allowed pressure drop to get the required internal diameter and copper tube size, check the flow and kW a pipe can carry, or use the Spitzglass formula in cubic feet per hour.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose the calculation

    Size, flow or Spitzglass.

  2. 2
    Enter the load and gas

    kW and type.

  3. 3
    Enter length and fittings

    m and count.

  4. 4
    Set the pressure drop

    mbar.

  5. 5
    Read bore and copper size

    With actual drop.

About this tool

A gas appliance needs its full flow at the right pressure, or it will burn poorly, light badly or lock out. Low-pressure gas pipes are therefore sized so that the pressure drop from the meter to the appliance stays small, in the UK typically no more than 1 mbar at full load. Pole's formula links flow, pipe bore, length, pressure drop and gas density, and allowing for elbows and tees by adding equivalent length gives a practical sizing method. This calculator finds the bore and the standard copper tube needed for a load, the flow a given pipe can carry, and the Spitzglass equivalent for US units.

Who this is for

Gas engineers and plumbers, heating designers, building services students and homeowners checking an installation proposal.

Load to flow

Gas flow (m³/h) = heat input (kW) / gross calorific value (kWh/m³). A 30 kW boiler on natural gas uses about 2.75 m³/h; on propane, about 1.13 m³/h. Add up all appliances that may run together.

Pole's formula

Q = 0.0071 × √(h × d⁵ / (s × L)) - h: pressure drop in mbar (usually 1 mbar from meter to appliance on natural gas). - d: internal diameter in mm. - s: relative density (natural gas about 0.6, propane about 1.5). - L: pipe length plus fittings in m; allow about 0.5 m per elbow or tee and 0.3 m per bend in small copper pipe. Because flow grows with d^2.5, a modest increase in bore carries much more gas.

Copper tube bores (EN 1057)

| Size | Bore | |---|---| | 15 mm | 13.6 mm | | 22 mm | 20.2 mm | | 28 mm | 26.2 mm | | 35 mm | 32.6 mm | | 42 mm | 39.6 mm |

Worked example

A 30 kW combi boiler on natural gas, 12 m of pipe with 6 fittings (15 m equivalent) and 1 mbar allowed, needs at least 16.8 mm bore, so 22 mm copper, with a drop of about 0.4 mbar. A 22 mm pipe 10 m long carries about 5.3 m³/h at 1 mbar, roughly 58 kW.

Spitzglass

In US practice, Q (ft³/h) = 3,550 × √(h × d⁵ / (S × L × (1 + 3.6/d + 0.03 d))) with h in inches of water column, d in inches and L in feet. Code tables such as NFPA 54 (National Fuel Gas Code) use related formulas and should be followed for installations.

Common mistakes

- Sizing for one appliance when several run together. - Forgetting fittings, which can add 20-50 % to the effective length. - Using nominal size instead of bore. - Ignoring the meter and regulator outlet pressure.

Limits

Low-pressure systems only. Gas work must be done by qualified, registered engineers following local regulations. This is not professional advice.

Worked example

30 kW boiler, natural gas, 15 m equivalent, 1 mbar: 16.8 mm bore, so 22 mm copper.

Quick facts

Frequently asked questions

How do I size a gas pipe for a boiler?

Convert kW to gas flow, add fittings to the length and apply Pole's formula.

What pressure drop is allowed?

Typically 1 mbar from meter to appliance on natural gas in the UK.

How much gas does a 30 kW boiler use?

About 2.75 m³/h of natural gas.

How much length does a fitting add?

About 0.5 m per elbow or tee in small copper pipe.

Why does propane need smaller pipes?

Its calorific value is about 2.5 times higher, so far less volume flows.

Is my data stored?

Pipe sizing inputs never leave this page.