Fire Load Density Calculator

List the combustible materials with their mass and calorific value, enter the floor area, and get the total fire load, the fire load density in MJ/m² and its wood equivalent, or use occupancy values.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose the method

    Inventory or occupancy.

  2. 2
    List the materials

    Mass and calorific value per line.

  3. 3
    Enter the floor area

    In m².

  4. 4
    Set factors

    Combustion and protection.

  5. 5
    Read the density

    MJ/m² and wood equivalent.

About this tool

Fire load is the total heat that the combustible contents of a room could release if they burned completely. Divided by the floor area, it gives the fire load density in MJ/m², the key input for fire resistance design, parametric fire curves and fire risk assessment. Each material contributes its mass times its net calorific value: wood about 17.5 MJ/kg, paper 20, most plastics 25-45. Eurocode EN 1991-1-2 also allows a combustion factor (0.8 for mainly cellulosic materials) and a factor for protected fire loads. This calculator sums your inventory, gives the density, the design value with factors, the equivalent in kilograms of wood per square metre and kWh/m², and offers the Eurocode's characteristic values for common occupancies.

Who this is for

Fire engineers, building control officers, insurers, facility managers, architects and students of fire safety.

Net calorific values (EN 1991-1-2 Table E.3)

| Material | Hu (MJ/kg) | |---|---| | Wood | 17.5 | | Paper, cardboard | 20 | | Cotton | 20 | | Wool | 23 | | Polyurethane | 23-25 | | PVC | 17-20 | | Polystyrene | 39-40 | | Polyethylene | 43-44 | | Rubber tyres | 30-32 | | Petrol, diesel | 44-45 |

Entering the inventory

One line per material: mass in kg and calorific value in MJ/kg. Include furniture, stored goods, linings and fixed combustibles.

Factors

- **Combustion factor m:** 0.8 for mainly cellulosic contents, 1.0 for others. - **Protection factor ψ:** 1.0 for unprotected loads; fire loads in closed containers designed to resist fire may be reduced. - EN 1991-1-2 also applies δ factors for compartment size, occupancy risk and active measures such as sprinklers.

Characteristic values by occupancy (EN 1991-1-2 Table E.4, 80 % fractile)

| Occupancy | q (MJ/m²) | |---|---| | Dwelling | 948 | | Hospital room | 280 | | Hotel room | 377 | | Library | 1,824 | | Office | 511 | | Classroom | 347 | | Shopping centre | 730 | | Theatre | 365 | | Transport (public space) | 122 |

Worked example

800 kg of wood furniture, 150 kg of paper, 60 kg of polystyrene and 40 kg of polyurethane foam in 50 m²: 20,400 MJ, 408 MJ/m² (23 kg of wood per m²). With m = 0.8, the design value is 326 MJ/m².

Using the result

Fire load density drives the duration and severity of a fully developed fire and the equivalent fire exposure time of structural elements. Higher fire loads call for longer fire resistance or more active protection.

Example uses

A fire engineer checks whether a library's book stock pushes the fire load above the design value. A warehouse manager compares storing plastics with storing paper. An insurer estimates the severity of a potential fire in an archive.

Fire load and fire duration

For a fire controlled by ventilation, the burning rate depends on the size of openings; a higher fire load mostly makes the fire last longer rather than burn hotter. Eurocode parametric curves combine fire load density and opening factor to estimate both.

Limits

Simple summation; burning rate, distribution and ventilation also matter. This is not professional fire engineering advice.

Worked example

20,400 MJ of contents in 50 m²: 408 MJ/m², 326 MJ/m² with m = 0.8.

Quick facts

Frequently asked questions

What is fire load density?

The total combustible energy in a space divided by its floor area, in MJ/m².

What is the calorific value of wood?

About 17.5 MJ/kg net.

What is a typical office fire load?

511 MJ/m² as the 80 % fractile in EN 1991-1-2.

What is the combustion factor?

A reduction for incomplete combustion, 0.8 for cellulosic materials.

Do plastics add more fire load than wood?

Yes, many plastics have twice the calorific value of wood.

Is my data stored?

No. The calculation runs in your browser.