Fire Extinguisher Quantity and Placement Calculator

Enter the floor area and hazard level with the extinguisher rating to get how many extinguishers NFPA 10 requires, or the total Class A rating and count under BS 5306-8.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Choose the standard

    NFPA 10 or BS 5306-8.

  2. 2
    Enter the floor area

    ft² or m².

  3. 3
    Set the hazard

    Light, ordinary or extra.

  4. 4
    Choose the rating

    Per extinguisher.

  5. 5
    Read the number

    Then check travel distances.

About this tool

Portable extinguishers tackle fires in their first minutes, but only if there are enough of them, of the right type, within easy reach. Standards set how many are needed. NFPA 10 in the United States rates extinguishers for Class A (ordinary combustibles) by numbers such as 2-A and 4-A, and limits the floor area each unit of rating may protect and the travel distance to an extinguisher. BS 5306-8 in the UK requires a total Class A rating of at least 0.065 times the floor area, with at least 26A on each storey. This calculator applies both methods and helps you choose between larger and smaller units.

Who this is for

Fire safety officers, facility managers, landlords, small business owners, fire equipment suppliers and students.

NFPA 10 Class A (Table 6.2.1.1)

| Occupancy hazard | Minimum rating | Max area per unit of A | Max area per extinguisher | Max travel | |---|---|---|---|---| | Light (low) | 2-A | 3,000 ft² | 11,250 ft² | 75 ft | | Ordinary (moderate) | 2-A | 1,500 ft² | 11,250 ft² | 75 ft | | Extra (high) | 4-A | 1,000 ft² | 11,250 ft² | 75 ft | Number needed = the larger of area / (rating × area per A) and area / 11,250, and enough units that nobody walks more than 75 ft to one.

Class B (flammable liquids)

NFPA 10 uses travel distance: for ordinary hazards, 10-B within 30 ft or 20-B within 50 ft; extra hazards need 40-B within 30 ft or 80-B within 50 ft.

BS 5306-8

Total Class A rating per storey ≥ 0.065 × floor area (m²), and at least 26A per storey; no more than 30 m travel to an extinguisher. With 13A water extinguishers, a 1,000 m² floor needs 65A, so five units.

Choosing types

| Fire | Suitable | |---|---| | A: wood, paper, textiles | Water, foam, multi-purpose powder | | B: flammable liquids | Foam, CO2, powder | | C: gases | Powder (after isolating the supply) | | Electrical equipment | CO2, powder | | F/K: cooking oil | Wet chemical | Avoid powder indoors where possible: it reduces visibility and damages equipment.

Worked example

A 10,000 ft² ordinary hazard warehouse with 2-A extinguishers: 10,000 / (2 × 1,500) = 3.3, so 4 units, placed so travel never exceeds 75 ft. With 4-A units, 2 would satisfy the area rule, but travel distance usually requires more.

Placement

Mount extinguishers on escape routes, near exits and specific hazards, with the top no higher than about 1.5 m (5 ft). Keep them visible and signed, and service them annually.

Example uses

A shop owner checks the number of extinguishers for a 600 m² store.

Limits

Area rules only; travel distance must be checked on the floor plan. This is not professional fire safety advice.

Worked example

NFPA 10 ordinary hazard, 10,000 ft², 2-A: 4 extinguishers.

Quick facts

Frequently asked questions

How many extinguishers does NFPA 10 require?

Based on rating, floor area per unit of A, 11,250 ft² per unit and 75 ft travel.

What does 2-A mean?

A Class A rating roughly equivalent to 2.5 gallons of water.

What is the BS 5306-8 rule?

Total Class A rating of at least 0.065 × floor area, minimum 26A per storey.

Which extinguisher for electrical fires?

CO2 or powder.

How far should people walk to an extinguisher?

No more than 75 ft (NFPA 10) or 30 m (BS 5306-8).

Is my data stored?

No. Building data is processed locally.