Earthing Conductor and Busbar Size Calculator

Enter the earth fault current and disconnection time to get the minimum protective conductor size, then check a busbar size against current and temperature rise.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Enter the fault

    Type the prospective earth fault current and the device disconnection time.

  2. 2
    Pick the conductor

    Choose the material and the conductor situation; edit the temperatures if needed.

  3. 3
    Read the size

    Check the minimum area, the next standard size and the table-method comparison.

  4. 4
    Check the time margin

    Use the size-against-time table to see how sensitive the result is.

  5. 5
    Estimate a busbar

    Open the Busbar tab, enter bar size, ambient and rise, or ask for a size for a current.

  6. 6
    Save and print

    Save a named scenario, then press Report and choose Save as PDF.

About this tool

Every circuit needs a protective conductor that can survive the earth fault current long enough for the fuse or breaker to clear it. If the conductor is too thin, it heats past the point where its insulation is damaged before the protective device opens, and the path that should keep exposed metal at safe voltage can fail. The wiring standards give two routes. The quick route is a table that ties the earth conductor size to the line conductor size. The more economical route is the adiabatic equation, S = √(I²t) / k, which assumes all the heat of a short fault stays in the copper and checks the final temperature. This calculator does the adiabatic sum for copper, aluminium and steel, works out the factor k from the material constants instead of copying a single number, compares it with the table method, and shows how the minimum size changes when the device takes longer to clear. A second tab estimates the steady current rating of a flat busbar in still air from a heat balance between the resistive loss and what the bar sheds by convection and radiation, so you can sanity-check a bar size before you ask a panel builder for a type-tested rating.

Choosing the right k

The k factor depends on the conductor metal, the temperature it starts at and the temperature its insulation tolerates at the end of the fault. A separate PVC-insulated copper conductor starts at 30 °C and may reach 160 °C, which gives k of about 143. The same copper as a core inside a PVC multicore cable is already at its 70 °C operating temperature, so k drops to about 115. Bare copper that touches nothing flammable can be allowed to reach 200 °C or more and k rises to 159. Pick the situation from the list and the initial and final temperatures fill in; you can then edit them for a special insulation. The Constants tab lists B, Qc and ρ20 for each metal and the k they produce for every situation, which is useful when checking someone else's calculation.

Fault current and time

Use the prospective earth fault current at the far end of the circuit and the time the protective device takes to disconnect at that current, read from its time-current curve. A low fault current often means a longer time, so check both ends of a circuit. The size-against-time table shows the trend: doubling the time raises the required area by about 41 %. The result tile also shows the longest time the chosen standard size can carry the current, so you can see how much margin you have.

Busbar estimate

The busbar tab balances I²R heating against natural convection from the bar faces and radiation from the surface. Emissivity matters: bright copper sheds much less heat by radiation than oxidised or painted bars, which is why painted bars carry more. Width mounted vertically cools better than a flat bar. For two or more bars per phase the inner faces mostly see each other, so the model counts only part of them. The AC to DC resistance ratio lets you allow for skin effect on wide or thick bars.

Limits

This is not a substitute for a licensed engineer's design. The adiabatic equation is valid for faults of up to about five seconds. The busbar figure is for a single run in still, open air; inside a switchboard the enclosure, neighbouring bars and joints change the rating, and IEC 61439 requires type-tested or verified ratings. Local wiring rules may also set minimum sizes that are larger than the calculated value.

Worked example

A sub-main has a prospective earth fault current of 6,000 A and its breaker clears in 0.4 s. With a separate PVC-insulated copper earth conductor, k = 226 × √ln((234.5 + 160)/(234.5 + 30)) = 142.7. The minimum area is √(6000² × 0.4) / 142.7 = 26.6 mm², so the next standard size is 35 mm², which could carry that current for 0.69 s. The table method with 35 mm² line conductors also gives 16 mm², which is too small here, so the adiabatic result decides. A single 40 × 10 mm oxidised copper bar edge-on, 35 °C ambient and 30 K rise, is estimated at about 780 A.

Quick facts

Frequently asked questions

When can I use the table method instead of the equation?

The table method (16 mm² line or less: same size; up to 35 mm²: 16 mm²; above: half) is always allowed as long as the earth conductor is the same metal as the line conductors. The adiabatic equation usually gives a smaller, cheaper conductor but needs the fault current and clearing time.

Which fault current should I enter?

The prospective earth fault current at the point being checked, usually calculated from the earth fault loop impedance, together with the disconnection time of the device at that current. The short-circuit calculator on this site can estimate the minimum single-phase fault.

Why is k lower for a core inside a cable?

Because the core is already at its operating temperature, typically 70 °C for PVC or 90 °C for XLPE, before the fault starts, so there is less temperature headroom before the insulation limit.

Is the busbar rating good enough for a switchboard?

No. It is a still-air estimate for planning. A switchboard must use the manufacturer's verified rating under IEC 61439, which accounts for the enclosure, joints and neighbouring heat sources.

Can I size steel earthing conductors?

Yes, for bare steel situations listed in the standard, such as earth electrodes or structural steel. Steel has a k of about 58 at 200 °C, so it needs roughly 2.7 times the copper area.

Are my inputs saved?

Yes, on this device only. Named scenarios, a JSON backup and a printable report keep your work; nothing is sent to a server.