Duct Sizing Calculator
Enter air flow and a design velocity or friction rate to size a round or rectangular duct, calculate pressure loss along a run with fittings and fan power, or convert rectangular ducts to equivalent round size.
Runs in your browser. Your files never leave your device. See how to check
…
How to do it
- 1Choose the method
Velocity, friction, loss or equivalent.
- 2Enter the air flow
m³/s.
- 3Set velocity or friction
m/s or Pa/m.
- 4Add length and fittings
For pressure loss.
- 5Read size and loss
And fan power.
About this tool
Ventilation and air-conditioning ducts are sized either for a target velocity, which controls noise, or for a constant pressure loss per metre, the equal friction method that balances most systems. This calculator does both. In velocity mode, it gives the round diameter and a rectangular size for a chosen aspect ratio with the resulting friction rate. In equal friction mode, it solves the Darcy-Weisbach equation with the Colebrook friction factor for the round duct that gives your friction rate, typically 0.8-1.2 Pa/m. A pressure loss mode adds fittings as loss coefficients and gives the fan power, and a conversion mode gives the equivalent round diameter of a rectangular duct by Huebscher's formula, which matches friction loss at the same flow.
Who this is for
HVAC designers, mechanical engineers, installers, energy auditors and building services students.
Recommended velocities
| Duct | Low noise | Typical | |---|---|---| | Main ducts, offices | 4-6 m/s | 6-8 m/s | | Branch ducts | 3-4 m/s | 4-6 m/s | | Residential | 2-3 m/s | 3-4 m/s | | Industrial exhaust | | 10-20 m/s |
Equal friction
A friction rate of about 1 Pa/m is common for low-pressure systems (0.08-0.15 in w.g. per 100 ft in US practice). Each duct section is sized for that rate, so longer runs need more balancing.
Pressure loss
Δp = f·(L/D)·½ρv² for straight ducts plus ΣK·½ρv² for fittings. Typical K: 90° smooth elbow 0.2-0.3, mitred elbow without vanes 1.2, branch take-off 0.5-1, grille 1-3.
Equivalent diameter
De = 1.30·(a·b)^0.625/(a + b)^0.25 gives the round duct with the same friction loss and flow as a rectangular a × b duct. A 300 × 200 mm duct equals a 266 mm round duct. Keep aspect ratios below about 4:1.
Worked example
1 m³/s at 5 m/s needs a 505 mm round duct or 632 × 316 mm rectangular at 2:1. At 1 Pa/m, the round duct is 441 mm with 6.5 m/s. A 30 m run of 500 mm duct with fittings totalling K = 2.5 loses 55 Pa, needing about 0.09 kW of fan power at 60 % efficiency.
Fan power
P = Q × Δp / η. The whole system pressure (ducts, filters, coils, terminals) sets the fan duty; specific fan power targets (W per L/s) appear in energy codes.
Common mistakes
- Using velocity alone for long runs, which can give high pressure losses and a larger fan than necessary. - Choosing very flat rectangular ducts: a 4:1 aspect ratio uses roughly 25-30 % more sheet metal than a 1:1 duct with the same capacity. - Forgetting fittings, which often account for half the system pressure loss. - Ignoring air leakage, which grows with pressure and duct class. - Placing fittings back to back, which makes the published K values unreliable.
Limits
Standard air (1.2 kg/m³), galvanised steel roughness; flexible ducts and high-pressure systems differ. This is not professional engineering advice.
Worked example
1 m³/s at 5 m/s: 505 mm round duct; 300 × 200 mm equals 266 mm round.
Quick facts
- Category: Engineering & Construction
- Works in your browser, no sign-up, no upload.
- Your input stays on your device.
- Available in English.
- Content last reviewed:
- Official source: Duct design (ASHRAE Handbook Fundamentals, ch. 21; CIBSE Guide C): sizing by velocity, equal friction with Darcy-Weisbach and Colebrook for air (ε = 0.09 mm galvanised steel), Huebscher equivalent diameter, fan power Q·Δp/η
Frequently asked questions
What velocity should a duct have?
About 4-8 m/s in commercial mains, lower for quiet spaces.
What is the equal friction method?
Sizing every section for the same pressure loss per metre.
How do I convert rectangular to round?
Use Huebscher's equivalent diameter.
What friction rate is typical?
Around 1 Pa/m for low-pressure systems.
How is fan power calculated?
Flow × pressure / efficiency.
Is my data stored?
Nothing is uploaded; scenarios stay in this browser.