Cable Size and Breaker Calculator (IEC 60364-5-52)

Enter the design current, installation method, ambient temperature, grouping, length and voltage, and get the smallest copper cable that carries the current, protects with a standard breaker and keeps voltage drop in limit.

Runs in your browser. Your files never leave your device. See how to check

…

How to do it

  1. 1
    Enter the design current

    In amps.

  2. 2
    Choose the installation

    Method A1, B1 or C.

  3. 3
    Set temperature and grouping

    Ambient and number of circuits.

  4. 4
    Enter length and voltage

    With power factor and limit.

  5. 5
    Read cable and breaker

    With voltage drop.

About this tool

Sizing a cable means satisfying two rules at once. It must carry the design current without overheating, which depends on how it is installed, the ambient temperature and how many other cables share the route; and the voltage at the far end must not drop too much. A protective device must then sit between the design current and the cable's capacity: Ib ≤ In ≤ Iz. This calculator uses the current-carrying capacities of IEC 60364-5-52 for copper PVC-insulated cables in reference methods A1 (in conduit in an insulated wall), B1 (in conduit on a wall) and C (clipped direct), applies the ambient temperature and grouping factors, picks the next standard breaker above the design current and finds the smallest cross-section from 1.5 to 120 mm² that meets both capacity and voltage drop.

Who this is for

Electricians, electrical designers, installers working to IEC-based wiring rules, students and building services engineers.

Steps

1. Design current Ib of the circuit. 2. Protective device rating In ≥ Ib (6, 10, 13, 16, 20, 25, 32, 40, 50, 63 A and up). 3. Corrected capacity Iz = tabulated capacity × temperature factor × grouping factor ≥ In. 4. Voltage drop ≤ the limit for the circuit.

Capacities (copper, PVC, 2 loaded conductors, 30 °C)

| mm² | A1 | B1 | C | |---|---|---|---| | 1.5 | 14.5 | 17.5 | 19.5 | | 2.5 | 19.5 | 24 | 27 | | 4 | 26 | 32 | 36 | | 6 | 34 | 41 | 46 | | 10 | 46 | 57 | 63 | | 16 | 61 | 76 | 85 | | 25 | 80 | 101 | 112 |

Correction factors

- Ambient (PVC): 25 °C 1.06, 35 °C 0.94, 40 °C 0.87, 45 °C 0.79, 50 °C 0.71. - Grouping (bunched or single layer): 2 circuits 0.80, 3 circuits 0.70, 4 circuits 0.65, 6 circuits 0.57, 9 circuits 0.50.

Voltage drop

u = b × (ρ1 × L/S × cosφ + λ × L × sinφ) × Ib, with b = 2 for single-phase and 1 for three-phase (phase-to-neutral), ρ1 = 0.0225 Ω·mm²/m for copper at operating temperature and λ = 0.08 mΩ/m. IEC 60364-5-52 Annex G suggests 3 % for lighting and 5 % for other uses on installations supplied from the public network.

Worked example

A 32 A single-phase circuit, clipped direct (method C), 30 m long at 230 V: 4 mm² carries 36 A on a 32 A breaker, with a voltage drop of about 4.5 %. With a 3 % limit, 6 mm² just passes at 2.99 %; at unity power factor, it gives 3.13 % and 10 mm² is needed.

Common mistakes

- Sizing only for current and forgetting voltage drop on long runs, which often decides the cable on circuits over about 25 m. - Applying the clipped-direct rating to a cable that later runs through loft insulation, where capacity can halve. - Ignoring grouping where several circuits share one trunking or tray. - Choosing a breaker larger than the corrected cable capacity, which leaves the cable unprotected against overload. - Forgetting that three-phase drop is quoted line-to-line, while this tool reports it against the voltage you enter.

Limits

Copper PVC cables and the listed methods only; national rules (BS 7671, NF C 15-100, VDE) may differ in detail. Earth fault loop impedance and short-circuit withstand are not checked. This is not professional advice; installations must be designed and verified by a qualified person.

Worked example

32 A, method C, 30 m at 230 V: 4 mm² copper on a 32 A breaker, 4.5 % voltage drop.

Quick facts

Frequently asked questions

What does Ib ≤ In ≤ Iz mean?

Design current ≤ breaker rating ≤ corrected cable capacity.

Why do installation methods differ?

Cables in insulation or conduit cannot shed heat as well as cables clipped in free air.

How much voltage drop is allowed?

Typically 3 % for lighting and 5 % for other circuits.

What does grouping do?

Cables bunched together heat each other, so their capacity is reduced.

Does this check earth fault protection?

No. Loop impedance must be checked separately.

Is my data stored?

No. The calculation runs in your browser.

Guides for this tool

Completely freeNo cost, no sign-up
Files stay privateEverything runs in your browser
Easy in your languageAvailable in many languages