How to Size a Grease Trap or Grease Interceptor for a Kitchen

Size a commercial kitchen grease trap from sinks, meals or peak flow, compare the PDI, UPC and EN 1825 methods and plan how often to pump it out.

Saizul Amin
Saizul Amin19 Nov 2026 · 4 min read
How to Size a Grease Trap or Grease Interceptor for a Kitchen

How to Size a Grease Trap or Grease Interceptor for a Kitchen

Fats, oils and grease poured down a kitchen sink are liquid while hot. A few metres down the drain they cool, stick to the pipe wall and catch everything else that passes. Sewer blockages and overflows from food businesses are common enough that almost every authority requires a grease trap or interceptor, sized to the kitchen. The difficulty is that there are several sizing methods, and which one applies depends on where you are.

Two kinds of device

Hydromechanical grease interceptors, often called grease traps, are compact units under or beside the sinks. They are rated by flow, in gallons per minute or litres per second, and by how much grease they can hold.

Gravity grease interceptors are large tanks, usually outside, sized by volume. Wastewater stays in them long enough for grease to float and solids to settle.

Method 1: fixtures and drain time

The fixture method, from the PDI G-101 standard used in North America, works from what drains into the unit. For each sink compartment:

  • Volume in US gallons = length × width × depth in inches / 231.
  • Assume it is 75 percent full.
  • Divide by the drain time, one minute for most sinks or two for large ones.

A three-compartment pot sink with 18 × 24 × 12 inch bowls holds 22.4 gallons per bowl, so each bowl drains at about 16.8 gpm and the three together at 50.5 gpm. Add a prep sink at 10.5 gpm and a mop sink at 3 gpm and the total is 64 gpm. The next standard rating is 75 gpm, and grease capacity is usually twice the rating in pounds, 150 lb.

Method 2: meals and retention for gravity interceptors

A formula widely printed with the Uniform Plumbing Code sizes gravity interceptors from the busiest hour:

size in gallons = meals in the peak hour × waste flow per meal × retention time × storage factor

Typical values are 6 gallons per meal with a dishwasher or 5 without, a 2.5 hour retention time, and a storage factor of 1 for 8 hours of trading rising to 1.5 for 12 hours. A restaurant serving 120 meals in its peak hour and open 12 hours needs 120 × 6 × 2.5 × 1.5 = 2,700 gallons, about 10,200 litres.

Method 3: EN 1825-2 nominal size

In Europe grease separators are rated by a nominal size NS, roughly their flow capacity in litres per second. EN 1825-2 calculates the maximum flow from meals as Qs = meals per day × water per meal × shock factor / (3600 × operating hours), then multiplies by factors for high temperature, heavy fats and detergents. A restaurant with 400 meals a day, 50 litres per meal, a shock factor of 8.5 and 12 hours of operation has Qs of about 3.9 L/s, which calls for NS 4, with a sludge trap of at least about 400 litres.

Method 4: flow times retention

Many water authorities simply ask for the peak hourly flow multiplied by a retention time, often one hour, with a minimum size for any food business. If you hold a trade waste permit, it usually says which figures to use.

How often to empty it

A grease trap that is too full lets grease through. A common rule is to pump out before grease and solids reach a quarter of the depth. If you can estimate the grease and solids produced per meal, the time to fill a quarter of the working volume follows. In practice, many authorities set a fixed interval, and a cleaning log is often a permit condition.

Using the calculator

The Grease Trap Sizing Calculator runs all four methods side by side. List the sinks and appliances for the fixture method, enter peak hour meals and factors for the gravity method, meals per day and factors for EN 1825-2, or peak flow and retention for the authority method. Each tab shows its working, a pump-out estimate covers the gravity, flow and hydromechanical sizes, and the sizing sheet prints all results with the fixture list. Factors are example values that your code edition or authority may set differently.

Before you buy

Confirm the method and figures with the plumbing inspector or water authority, check where the interceptor can go and how it will be emptied, make sure WCs and surface water bypass it, and choose a unit tested to the relevant standard.