Duct Sizing Calculator
Enter air flow and a design velocity or friction rate to size a round or rectangular duct, calculate pressure loss along a run with fittings and fan power, or convert rectangular ducts to equivalent round size.
Chạy trong trình duyệt của bạn. Tệp không bao giờ rời khỏi thiết bị. Xem cách tự kiểm tra
…
Cách thực hiện
- 1Choose the method
Velocity, friction, loss or equivalent.
- 2Enter the air flow
m³/s.
- 3Set velocity or friction
m/s or Pa/m.
- 4Add length and fittings
For pressure loss.
- 5Read size and loss
And fan power.
Giới thiệu công cụ này
Ventilation and air-conditioning ducts are sized either for a target velocity, which controls noise, or for a constant pressure loss per metre, the equal friction method that balances most systems. This calculator does both. In velocity mode, it gives the round diameter and a rectangular size for a chosen aspect ratio with the resulting friction rate. In equal friction mode, it solves the Darcy-Weisbach equation with the Colebrook friction factor for the round duct that gives your friction rate, typically 0.8-1.2 Pa/m. A pressure loss mode adds fittings as loss coefficients and gives the fan power, and a conversion mode gives the equivalent round diameter of a rectangular duct by Huebscher's formula, which matches friction loss at the same flow.
Who this is for
HVAC designers, mechanical engineers, installers, energy auditors and building services students.
Recommended velocities
| Duct | Low noise | Typical | |---|---|---| | Main ducts, offices | 4-6 m/s | 6-8 m/s | | Branch ducts | 3-4 m/s | 4-6 m/s | | Residential | 2-3 m/s | 3-4 m/s | | Industrial exhaust | | 10-20 m/s |
Equal friction
A friction rate of about 1 Pa/m is common for low-pressure systems (0.08-0.15 in w.g. per 100 ft in US practice). Each duct section is sized for that rate, so longer runs need more balancing.
Pressure loss
Δp = f·(L/D)·½ρv² for straight ducts plus ΣK·½ρv² for fittings. Typical K: 90° smooth elbow 0.2-0.3, mitred elbow without vanes 1.2, branch take-off 0.5-1, grille 1-3.
Equivalent diameter
De = 1.30·(a·b)^0.625/(a + b)^0.25 gives the round duct with the same friction loss and flow as a rectangular a × b duct. A 300 × 200 mm duct equals a 266 mm round duct. Keep aspect ratios below about 4:1.
Worked example
1 m³/s at 5 m/s needs a 505 mm round duct or 632 × 316 mm rectangular at 2:1. At 1 Pa/m, the round duct is 441 mm with 6.5 m/s. A 30 m run of 500 mm duct with fittings totalling K = 2.5 loses 55 Pa, needing about 0.09 kW of fan power at 60 % efficiency.
Fan power
P = Q × Δp / η. The whole system pressure (ducts, filters, coils, terminals) sets the fan duty; specific fan power targets (W per L/s) appear in energy codes.
Common mistakes
- Using velocity alone for long runs, which can give high pressure losses and a larger fan than necessary. - Choosing very flat rectangular ducts: a 4:1 aspect ratio uses roughly 25-30 % more sheet metal than a 1:1 duct with the same capacity. - Forgetting fittings, which often account for half the system pressure loss. - Ignoring air leakage, which grows with pressure and duct class. - Placing fittings back to back, which makes the published K values unreliable.
Limits
Standard air (1.2 kg/m³), galvanised steel roughness; flexible ducts and high-pressure systems differ. This is not professional engineering advice.
Ví dụ có lời giải
1 m³/s at 5 m/s: 505 mm round duct; 300 × 200 mm equals 266 mm round.
Tóm tắt
- Danh mục: Kỹ thuật và xây dựng
- Chạy trong trình duyệt, không đăng ký, không tải lên.
- Thông tin bạn nhập ở lại trên thiết bị.
- Có bằng tiếng Anh.
- Nội dung được rà soát lần cuối:
- Nguồn chính thức: Duct design (ASHRAE Handbook Fundamentals, ch. 21; CIBSE Guide C): sizing by velocity, equal friction with Darcy-Weisbach and Colebrook for air (ε = 0.09 mm galvanised steel), Huebscher equivalent diameter, fan power Q·Δp/η
Câu hỏi thường gặp
What velocity should a duct have?
About 4-8 m/s in commercial mains, lower for quiet spaces.
What is the equal friction method?
Sizing every section for the same pressure loss per metre.
How do I convert rectangular to round?
Use Huebscher's equivalent diameter.
What friction rate is typical?
Around 1 Pa/m for low-pressure systems.
How is fan power calculated?
Flow × pressure / efficiency.
Is my data stored?
Nothing is uploaded; scenarios stay in this browser.