Pressure Relief Valve Sizing Calculator (API 520)
Enter the relieving load for gas or vapour, steam or liquid, the set pressure, overpressure and back pressure, and the coefficients Kd, Kb, Kc and Kw. The tool applies the API 520 Part I sizing equations to every relief case, picks the governing case and the API 526 orifice letter, shows the percent of the orifice used and checks back pressure and inlet loss.
Tarayıcınızda çalışır. Dosyalarınız cihazınızdan asla çıkmaz. Nasıl kontrol edeceğinizi görün
…
Nasıl yapılır
- 1Choose the service
Pick gas or vapour, steam or liquid, the valve type and the pressure unit you use.
- 2Set the pressures
Type the set pressure, built-up and superimposed back pressure and the inlet line loss.
- 3List relief cases
Add each case with its relieving load, allowable overpressure and relieving temperature.
- 4Enter properties
Type molar mass, Z and k for gas, or specific gravity and viscosity for liquid.
- 5Enter coefficients
Replace Kd, Kb, Kc and Kw with the certified values of the valve you plan to use.
- 6Read and print
Check the governing case, orifice letter and warnings, then print the sizing sheet.
Bu araç hakkında
A pressure relief valve is the last line of defence when a vessel, boiler or pipe system is overpressured by a blocked outlet, a failed control valve, a fire or a runaway reaction. It must open at its set pressure and pass the full relieving load before the pressure rises beyond the allowed overpressure, usually 10 percent for a single valve, 16 percent for several valves and 21 percent in a fire. API Standard 520 Part I gives the sizing equations that most refineries, chemical plants and many other industries use, and API 526 lists the standard orifice letters from D to T with their effective areas. This calculator implements those equations. For gases and vapours it checks whether the flow is critical, comparing the back pressure with the critical pressure ratio from the specific heat ratio, and uses the critical flow equation with the coefficient C, or the subcritical equation with the factor F2. For steam it offers the Napier equation with the high pressure factor KN and the superheat factor KSH, or a direct integration of an isentropic nozzle using IAPWS-IF97. For liquids it uses the equation for valves certified on liquid, with an optional viscosity correction from the Reynolds number.
Relief cases and the result
List every credible relief case with its load, allowable overpressure and relieving temperature. The tool computes the required effective area for each, takes the largest as the governing case, and selects the smallest API 526 letter whose effective area covers it. It reports the percent of the orifice used and the approximate rated capacity of that orifice at the governing conditions, and the orifice tab lists every letter with the capacity it would give. Results are in SI or US units.
Coefficients and checks
The effective coefficient of discharge Kd starts at 0.975 for gas and steam and 0.65 for liquid, and Kb, Kw and Kc at 1; type 0.9 for Kc when a rupture disk sits under the valve. These defaults are the usual starting values in API 520, but the certified coefficients and back pressure correction curves of the valve you buy must replace them. The tool warns when the inlet line loss exceeds 3 percent of set pressure and when built-up back pressure exceeds 10 percent for a conventional valve. For superheated steam, KSH is estimated from the ratio of IF97 nozzle fluxes at the actual and the saturated state, which you can override.
Limits
This calculator sizes a valve for a load you supply; it does not calculate the relief load itself, the fire heat input, two-phase or flashing flow, the outlet piping, reaction forces or noise. It does not cover rupture disk sizing on its own. Results do not satisfy any pressure equipment code on their own and must be checked by a qualified engineer.
Çözümlü örnek
A separator relieves 11,010 kg/h of hydrocarbon vapour with a molar mass of 51, Z = 0.90 and k = 1.11 at 75 °C in a blocked outlet case. The set pressure is 5.17 bar g and the overpressure 10 percent, so the relieving pressure is 670 kPa absolute; the 0.2 bar built-up back pressure leaves the flow critical. With C = 0.0249, Kd = 0.975 and Kb = Kc = 1, the required area is about 1678 mm², or 2.60 in². The control valve failure case of 8,000 kg/h needs 1220 mm² and the fire case of 9,000 kg/h at 21 percent overpressure and 95 °C needs 1300 mm². The governing blocked outlet case calls for an L orifice of 1841 mm², used to 91 percent.
Kısaca
- Kategori: Mühendislik ve inşaat
- Tarayıcınızda çalışır, kayıt yok, yükleme yok.
- Girdiğiniz bilgiler cihazınızda kalır.
- İngilizce olarak mevcut.
- İçeriğin son gözden geçirilmesi:
- Resmî kaynak: API Standard 520 Part I sizing equations; API Standard 526 effective orifice areas; IAPWS-IF97 for steam
Sık sorulan sorular
What does the orifice letter mean?
API 526 standardises flanged steel relief valves with orifice letters D, E, F, G, H, J, K, L, M, N, P, Q, R and T, each with a fixed effective area from 0.110 in² to 26.0 in². You choose the smallest letter whose area covers the required area.
When is gas flow critical?
When the absolute back pressure is below the critical pressure ratio times the relieving pressure, about 0.53 to 0.58 for most gases. The flow through the nozzle is then sonic and the critical flow equation applies.
What is Kb?
Kb corrects the capacity of balanced bellows or pilot valves for back pressure, read from the maker's curve. For conventional valves in critical flow Kb is 1, and subcritical flow is handled by the F2 factor instead.
How do I size a steam safety valve?
Choose steam, enter the load in kg/h or lb/h, the set pressure and the relieving temperature. Saturated steam uses the Napier equation directly; superheated steam adds KSH, which the tool can estimate, or you can use the direct integration method.
Can I use it for a boiler under ASME Section I?
The equations are similar, but boiler codes have their own capacity rules and certification. Use this for an independent check and follow the code and the valve maker for the actual selection.
What overpressure should I use?
Usually 10 percent of the maximum allowable working pressure for a single valve, 16 percent for multiple valves and 21 percent for fire cases. The code that applies to your equipment sets the limit.