Refrigerant PT Chart and Superheat Subcooling Calculator
Pick a refrigerant, type the suction and liquid line pressures from your gauges and the two line temperatures, and get the saturation temperatures, superheat and subcooling against the TXV target or the fixed orifice formula. R-744 is computed from a published equation; for other refrigerants you enter the maker's PT chart once, and nothing is shown as in range until it is checked.
Berjalan dalam pelayar anda. Fail anda tidak pernah meninggalkan peranti. Lihat cara menyemaknya
…
Cara melakukannya
- 1Choose the refrigerant
Pick it from the list and set the pressure unit and the temperature unit you use on site.
- 2Enter the PT data
For refrigerants other than CO2, paste or import the maker's PT chart on the PT data tab, name it and tick it as checked.
- 3Enter the gauge readings
Type the suction and liquid line pressures as they appear on your manifold or digital gauges.
- 4Enter the line temperatures
Type the suction and liquid line temperatures from a clamp-on probe placed close to the service valves.
- 5Set the target and read
Type the nameplate subcooling or the fixed orifice conditions, then compare superheat and subcooling with the targets.
- 6Log and print
Add the reading to the service log with its PT data source, print the check sheet or export the log as CSV.
Tentang alat ini
Charging an air conditioner, heat pump or refrigeration system correctly comes down to two numbers. Superheat is how many degrees the suction vapour is above its saturation temperature where it leaves the evaporator; subcooling is how many degrees the liquid is below its saturation temperature where it leaves the condenser. Both need the saturation temperature at the pressure on your gauge, which is what a pressure-temperature (PT) chart gives. Because these two numbers decide whether refrigerant is added or removed, this tool only works from PT data with a known source. For R-744, carbon dioxide, the saturation pressure is computed from the vapour pressure equation published by Span and Wagner in 1996, from the triple point to the critical point at 30.98 °C. For R-410A, R-32, R-134a, R-22, R-404A, R-407C, R-454B, R-290 and R-600a the tool has no built-in table: you paste or import the PT chart from the refrigerant supplier or the equipment maker, in °C or °F and in psig, bar, kPa or MPa, gauge or absolute. Blends keep the bubble (liquid) and dew (vapour) columns separately, superheat uses the dew point and subcooling the bubble point.
How your PT table is used
A table needs at least three rows with rising temperatures and pressures; blends need both pressure columns, and the bubble pressure may not be below the dew pressure. Name the source, such as the maker and the chart edition, and tick that you checked every row against it. Until then the tool shows the readings as unverified and never as in range, and with no table it says incomplete — enter PT data from the manufacturer. Values are interpolated smoothly in the logarithm of pressure against the inverse of absolute temperature and are never extrapolated beyond the first and last rows. Tables are kept in this browser and shared with the line set calculator, and you can export them as CSV.
Targets
A TXV or electronic valve is charged to the subcooling on the nameplate, so you type that target. A fixed orifice or piston is charged to a target superheat that depends on the indoor wet bulb and outdoor dry bulb; the tool offers the widely printed field approximation, three times the wet bulb minus 80 minus the dry bulb, all halved, in °F, as an example, and warns below about 5 °F, where makers usually say to weigh in the charge.
Limits
This tool does not replace the maker's charging chart or procedure and does not know your unit. It does not handle transcritical CO2 above 31 °C. Readings depend on calibrated gauges, a clamp-on thermometer placed close to the service valves and stable running conditions; check airflow, filters and coils before changing the charge. Handling refrigerants requires the licence or certification your country asks for.
Contoh berselesaian
A technician checks a CO2 cold room circuit with an electronic expansion valve. The suction gauge reads 26.5 bar g and the suction line 2 °C below zero; the liquid line reads 48 bar g at 10.5 °C. From the Span and Wagner equation the evaporating temperature is −8.7 °C and the condensing temperature 13.5 °C, so superheat is 6.7 K and subcooling 3.0 K. Against the maker's targets of 6 K and 3 K with a 2 K tolerance, both readings are in range. On an R-410A unit the same steps work only after the technician pastes the maker's PT chart and ticks it as checked; before that the tool shows incomplete and offers the PT data tab.
Ringkasnya
- Kategori: Kejuruteraan & pembinaan
- Berjalan dalam pelayar, tanpa pendaftaran, tanpa muat naik.
- Maklumat yang anda masukkan kekal pada peranti anda.
- Tersedia dalam bahasa Inggeris.
- Kandungan disemak kali terakhir:
- Sumber rasmi: Span and Wagner (1996) CO2 vapour pressure equation; ASHRAE Standard 34 safety groups; other refrigerants from the user's manufacturer PT chart
Soalan lazim
Which pressure do I use for superheat and which for subcooling?
Superheat uses the suction (low side) pressure and the suction line temperature near the evaporator outlet or the outdoor unit service valve. Subcooling uses the liquid (high side) pressure and the liquid line temperature near the condenser outlet.
Why does the tool ask me for a PT table?
Superheat and subcooling decide the charge, so the saturation data must come from a known source. Only CO2 is computed from a published equation here; for every other refrigerant you enter the supplier's or maker's PT chart once and it is reused.
What do incomplete and unverified mean?
Incomplete means there is no PT data for that refrigerant, so no temperatures are shown. Unverified means you entered a table but have not named its source and ticked it as checked, so values are shown but never marked as in range.
Why are there bubble and dew columns?
Blends such as R-407C boil over a range of temperatures at one pressure. The dew point is where the last liquid boils off and is used for superheat; the bubble point is where the first vapour forms and is used for subcooling.
Can I paste a chart in psig and °F?
Yes. Choose the chart's temperature and pressure units before you paste, and the atmosphere its gauge values refer to. The tool converts every row to °C and kPa absolute and keeps the original order of bubble and dew.
What does high superheat with low subcooling mean?
Both readings together usually point to a low charge or a restriction in the liquid line. Check for leaks and restrictions before adding refrigerant; airflow problems can produce similar numbers.