Refrigerant Line Set Sizing and Charge Calculator
Enter the capacity of a split air conditioner or heat pump, the refrigerant, the one-way line length, fittings and lift. Every tube size is checked for velocity, pressure drop and the saturation temperature it costs, with oil return and flash gas warnings, and the extra charge for the length above the factory pre-charge is worked out in grams and ounces.
Berjalan dalam pelayar anda. Fail anda tidak pernah meninggalkan peranti. Lihat cara menyemaknya
…
Cara melakukannya
- 1Choose the refrigerant
Pick the refrigerant and the tube sizes, inch ACR or metric, and the length unit.
- 2Enter the duty
Type the capacity and the evaporating and condensing temperatures of the system.
- 3Describe the run
Enter the one-way length, equivalent length of bends and valves, and the lift between units.
- 4Compare tube sizes
Read velocity, pressure drop and saturation temperature loss for every suction and liquid size.
- 5Work out the charge
Enter the pre-charged length and, if known, the maker's grams per metre for the extra charge.
- 6Print the sheet
Print the line set sheet with both tables or export them as CSV for the job file.
Tentang alat ini
Split systems come with a pre-charge that covers a set length of pipe, often 5 to 7.5 metres. Longer runs need more refrigerant, and runs that climb or drop need the right pipe sizes: a suction line that is too large lets oil settle and starve the compressor, one that is too small costs capacity, and a liquid line with too much friction or lift can flash before the expansion valve. Installation manuals give a table of allowed sizes and a charge per metre, but they are often missing on site or the run is unusual. This calculator shows what is happening in the pipe. It turns the capacity into a refrigerant mass flow from the refrigeration effect, then for every standard tube size computes the velocity, the Reynolds number and the friction pressure drop with the Churchill friction factor, and converts the pressure drop into the drop in saturation temperature using your PT table from the maker's chart, shared with the PT chart tool. Without a checked table the temperature penalties, the flash check and the size suggestions are shown as incomplete or unverified. For the suction line it flags whether the velocity is high enough for oil to return in horizontal runs and in risers. For the liquid line it adds the static head of the lift and compares the total with the subcooling you measured, so you can see if liquid will flash.
Additional charge
If your manual gives an extra charge per metre, type it and the tool multiplies it by the length above the pre-charged length. If not, it estimates the charge from the inside volume of the liquid line filled with liquid refrigerant at the example density. Because the suction line also holds some vapour and the oil holds some refrigerant, makers' figures are usually close to this estimate but not identical; always prefer the manual and finish by checking superheat or subcooling.
Example values
The refrigeration effect, vapour and liquid densities and viscosities on the properties tab are example values for about 5 °C evaporating and 40 °C condensing with 5 K of superheat and subcooling, and the tube walls are typical ACR and metric refrigeration tube walls. Change them for other conditions. The suggested sizes use common rules of thumb: about 1 K loss in the suction line and 0.5 K friction loss in the liquid line, 3.8 m/s in horizontal suction lines and 7.6 m/s in risers.
Limits
This tool is not a substitute for the maker's maximum length, lift and pipe size limits, which take account of the compressor and controls. It does not model oil traps, double risers, multi-split branch kits, VRF systems or CO2, and it does not know about charge limits for flammable A2L and A3 refrigerants in occupied rooms.
Contoh berselesaian
A 7 kW R-410A heat pump is installed with 15 m of pipe one way, about 3 m of equivalent length in bends and a 3 m lift up to the indoor unit, with 5 K of subcooling at the outdoor unit. With the example refrigeration effect of 165 kJ/kg the mass flow is about 153 kg/h, and with the example vapour density a 5/8 in suction line runs at about 7.5 m/s while a 3/8 in liquid line runs at under 1 m/s. The pressure drops become saturation temperature losses once the installer pastes the maker's R-410A PT chart and ticks it as checked; until then those columns say incomplete and no size is suggested. With 7.5 m pre-charged and no maker's figure, the extra 7.5 m at the estimated 49 g/m from the example liquid density comes to about 368 g, which the installer replaces with the manual's grams per metre.
Ringkasnya
- Kategori: Kejuruteraan & pembinaan
- Berjalan dalam pelayar, tanpa pendaftaran, tanpa muat naik.
- Maklumat yang anda masukkan kekal pada peranti anda.
- Tersedia dalam bahasa Inggeris.
- Kandungan disemak kali terakhir:
- Sumber rasmi: Darcy-Weisbach pressure drop with the Churchill (1977) friction factor; ASHRAE Refrigeration Handbook piping practice (oil return velocity); example refrigerant properties
Soalan lazim
How much refrigerant do I add for a longer line set?
Multiply the length beyond the pre-charged length by the charge per metre from the installation manual. If you do not have it, the tool estimates it from the liquid line inside volume; weigh it in and confirm with superheat or subcooling.
Why does the suction line need a minimum velocity?
Compressor oil travels round the system with the refrigerant. In a vertical suction riser the vapour must move fast enough, about 7.6 m/s, to carry the oil up; otherwise oil collects in the evaporator and the compressor runs short of it.
What does the saturation temperature loss mean?
Friction lowers the pressure, and a lower suction pressure means a lower saturation temperature at the compressor. One kelvin of loss in the suction line costs a few percent of capacity, which is why lines are sized for about 1 K.
Why does lift matter for the liquid line?
Liquid refrigerant is dense, so pushing it up a few metres costs a noticeable pressure. If the pressure falls below the saturation pressure the liquid flashes to vapour and the expansion valve is starved, so you need enough subcooling.
Can I use the inch and metric tube sizes?
Yes. Choose ACR inch tube or metric tube at the top. The tube table on the properties tab shows the outside diameter, wall and inside diameter used.
Does it work for R-32 and R-454B?
Yes, both are in the list with example properties. These refrigerants are mildly flammable, so also check the room size and charge limits in the manual and in the safety standard.