Expansion Vessel Sizing Calculator
Enter the system water volume or let the tool estimate it from radiator and underfloor outputs, the fill and maximum temperatures, the static height and the safety valve setting. It works out the expansion volume, water reserve, pre-charge, final pressure and the vessel size to buy, then prints a sizing sheet.
Berjalan dalam pelayar anda. Fail anda tidak pernah meninggalkan peranti. Lihat cara menyemaknya
…
Cara melakukannya
- 1Choose the system
Pick sealed heating or chilled water, or potable hot water with an unvented cylinder.
- 2Enter the water volume
Type the volume or list the radiators, underfloor circuits and fan coils to estimate it.
- 3Set the temperatures
Type the cold fill temperature and the highest operating temperature, plus any glycol percentage.
- 4Add the pressures
Enter the static height above the vessel and the safety or expansion relief valve setting.
- 5Read the vessel size
Check the minimum volume, the selected vessel, the pre-charge and the cold fill pressure.
- 6Print the sheet
Print the sizing sheet or save it as CSV and keep it with the commissioning records.
Tentang alat ini
Water grows by about three percent when it is heated from a cold fill to 80 °C. In an open system the extra water rises into a feed and expansion tank, but almost every modern boiler, heat pump and unvented cylinder is sealed, so the extra volume has to go into a diaphragm expansion vessel. If the vessel is too small, the pressure climbs at every heat-up until the safety valve lifts and the system slowly loses water; if the pre-charge is wrong, the vessel is useless even when its size is right. This calculator follows the method of EN 12828 Annex D that installers across Europe use for heating and chilled water systems. It computes the expansion coefficient from real water densities, adds a water reserve so the system does not fall below its minimum pressure as it cools or loses a little water, sets the pre-charge from the static height above the vessel plus a margin, takes the final pressure from the safety valve setting minus its closing margin, and returns the nominal volume with Boyle's law. A second mode does the same job for unvented domestic hot water cylinders, where the vessel sits on the cold feed and its pre-charge equals the incoming pressure from the reducing valve.
The method in short
The expansion volume is the system volume multiplied by the expansion coefficient between the fill temperature and the highest operating temperature; glycol raises it. The water reserve is 0.5 percent of the system volume with a minimum of 3 litres. The pre-charge is the static height in metres divided by ten plus 0.2 bar. The final pressure is the safety valve setting minus 0.5 bar for valves up to 5 bar, or 90 percent of the setting above that. The nominal vessel volume is the expansion volume plus the reserve, multiplied by the absolute final pressure and divided by the difference between final pressure and pre-charge. The tool then picks the next size from the list and gives the cold fill pressure that leaves the reserve inside the vessel.
Estimating the water volume
If you do not know the system volume, list the emitter outputs: steel panel radiators, cast iron radiators, underfloor circuits and fan coils, each with a typical water content per kilowatt, plus the boiler, buffer and pipework. These litres-per-kilowatt figures, the glycol multipliers and the vessel size list are example values on the second tab that you can change to match the maker's data.
Limits
The water density comes from IAPWS-IF97, but the rest of the method is a design aid, not a certificate. It does not cover systems above 100 °C, where vapour pressure must be added, pressurisation units with pumps, solar thermal stagnation volumes or multiple vessels at different heights. Always set the pre-charge with the system pressure released, and keep within the pressure and temperature ratings printed on the vessel.
Contoh berselesaian
A house has 12 kW of steel panel radiators and a 3 kW underfloor heating circuit in the kitchen, with about 25 litres in the boiler and pipes. The estimate gives 96 + 51 + 25 = 172 litres. Heating from a 10 °C fill to 80 °C gives an expansion coefficient of 2.87 percent, so the expansion volume is 4.94 litres; the water reserve takes the 3 litre minimum. The top radiator is 8 m above the vessel, so the pre-charge is 1.0 bar, and the 3 bar safety valve gives a final pressure of 2.5 bar. The nominal volume is (4.94 + 3) × 3.5 / 1.5 = 18.5 litres, so a 25 litre vessel is chosen, filled cold to about 1.6 bar.
Ringkasnya
- Kategori: Kejuruteraan & pembinaan
- Berjalan dalam pelayar, tanpa pendaftaran, tanpa muat naik.
- Maklumat yang anda masukkan kekal pada peranti anda.
- Tersedia dalam bahasa Inggeris.
- Kandungan disemak kali terakhir:
- Sumber rasmi: EN 12828 Annex D expansion vessel method; IAPWS-IF97 water density
Soalan lazim
What pre-charge should my expansion vessel have?
For a sealed heating system, set it to the static height of water above the vessel in metres divided by ten, plus about 0.2 bar. A vessel with the top radiator 8 m above it needs about 1.0 bar.
Why is the vessel bigger than the expansion volume?
The diaphragm can only take in water until the gas cushion is compressed to the final pressure. With a 1 bar pre-charge and 2.5 bar final pressure only 43 percent of the vessel is usable, so the vessel must be about 2.3 times the volume it has to absorb.
Does antifreeze change the size?
Yes. Water and glycol mixtures expand more than water. The tool multiplies the expansion coefficient by an editable glycol factor, for example 1.2 at 20 percent glycol; use the glycol maker's expansion data for an exact figure.
How is a hot water cylinder vessel different?
On an unvented cylinder the vessel connects to the cold supply, so its pre-charge equals the outlet pressure of the pressure reducing valve, often 3 bar. There is no water reserve, and the final pressure comes from the expansion relief valve.
What happens if the vessel is too small?
Pressure rises sharply as the system heats, the safety valve may drip or open, and the system loses water. The boiler pressure gauge then falls when it cools, and air can be drawn in at high points.
Can I use it for chilled water?
Yes. Enter the lowest temperature as the fill temperature and the highest temperature the water can reach while the plant is off, often the plant room temperature, as the maximum temperature.