Grease Trap Sizing Calculator

Size the grease interceptor for a commercial kitchen four ways: from the sinks and fixtures that drain into it, from meals in the peak hour for a gravity interceptor, by the EN 1825-2 nominal size, or from the peak flow and a retention time. See every step, estimate how often it needs pumping and print a sizing sheet for the plumber or the water authority.

브라우저에서 실행됩니다. 파일은 기기 밖으로 나가지 않습니다. 확인하는 방법 보기

…

사용 방법

  1. 1
    Name the kitchen

    Type the site name that should appear on the sizing sheet you print.

  2. 2
    List the fixtures

    On the fixtures tab enter each sink compartment size or a fixed flow for appliances.

  3. 3
    Try the meals method

    Enter the meals in the peak hour, waste flow, retention time and storage factor.

  4. 4
    Check EN 1825-2

    Enter meals per day, water per meal, shock factor, hours and the three factors.

  5. 5
    Apply local rules

    Use the flow tab for the authority's retention time and minimum size, and review pump-outs.

  6. 6
    Print the sheet

    Print the sizing sheet with all four methods and the fixture list, or save it as CSV.

이 도구 소개

Fats, oils and grease from kitchens cool in the sewer, stick to the pipe and cause blockages and overflows, so restaurants, cafes, hotels and canteens must fit a grease trap or grease interceptor. Who decides the size depends on where you are: in the US the plumbing code and the local pretreatment programme, in Europe EN 1825 and the national annex, in Australia and many other countries the water authority's trade waste rules. This calculator collects the common methods in one place so you can compare them. The fixture method, used for hydromechanical interceptors that sit under or next to the sinks, adds up the volume of each sink compartment, assumes it is 75 percent full and drains in one or two minutes, and gives the flow rating in gallons per minute; the grease capacity is usually twice the rating in pounds. The meals method for in-ground gravity interceptors multiplies the meals served in the peak hour by the waste flow per meal, the retention time and a storage factor for the hours of operation. EN 1825-2 finds the nominal size NS from the maximum flow and factors for temperature, fat density and detergents.

Flow and retention time

Many water authorities set a minimum arrestor size and ask for the peak hourly flow multiplied by a retention time, often an hour. The fourth tab does this sum with a minimum you can set from your permit, so the figure matches what the inspector will check.

Pump-out interval

A grease trap that is too full lets grease through. A common rule is to pump it before grease and solids reach a quarter of the depth. Enter the meals per day and an estimate of grease and solids per meal and the tool estimates the days between pump-outs for the gravity and flow-based sizes, and how long a hydromechanical unit takes to reach its rated grease capacity. These are planning figures; keep a cleaning log and follow the authority's interval.

Example factors

The waste flow per meal, retention time and storage factors follow the values commonly printed with the Uniform Plumbing Code formula. The EN 1825-2 water per meal, shock factors, temperature, density and detergent factors and the sludge trap and grease storage multipliers are typical published figures. All of them are editable example values, and the code edition and the authority decide which apply.

Limits

The tool does not design venting, sampling points, flow control fittings, the location of the interceptor or the connections that must bypass it, such as WCs. It is not an approval and does not replace the authority's own sizing rules.

풀이 예시

A restaurant kitchen has a three-compartment pot sink with 18 × 24 × 12 inch bowls, an 18 × 18 × 10 inch prep sink and a mop sink rated at 3 gpm. Each pot sink bowl holds 22.4 gallons, 16.8 gpm at a one-minute drain; the three bowls give 50.5 gpm, the prep sink 10.5 gpm and the mop sink 3 gpm, a total of 64.0 gpm, so a 75 gpm hydromechanical interceptor with 150 lb grease capacity is needed. As a gravity interceptor, 120 meals in the peak hour × 6 gallons × 2.5 hours × 1.5 for 12 hours of trading gives 2,700 gallons. By EN 1825-2, 400 meals a day at 50 litres each with a shock factor of 8.5 over 12 hours give Qs = 3.94 L/s and NS 4.

한눈에 보기

자주 묻는 질문

What size grease trap does a restaurant need?

It depends on the method your authority uses. Under-sink units are rated in gpm or litres per second from the fixtures; in-ground interceptors are sized in gallons or litres from meals or flow. Run the methods here and use the one your code names.

How is a grease trap different from a grease interceptor?

The names overlap. Small hydromechanical units near the sinks are often called traps; larger gravity tanks outside the building are often called interceptors. Both separate grease by letting it float and cool.

Should a dishwasher drain to the grease trap?

Rules differ. Some authorities require it, others forbid it because hot water and detergents push grease through. The detergent factor in the EN method and the waste flow choice in the meals method account for dishwashers.

How often must it be pumped?

Many authorities require cleaning when grease and solids fill 25 percent of the depth, or at a fixed interval such as every one to three months. The tool estimates the interval from the meals and an editable grease per meal figure.

Can I use litres and metric sizes?

Yes. The fixture method works in inches and gpm because PDI ratings use them, but it also shows litres per second; the meals result is given in gallons and litres, and the EN and flow methods work in litres.

What is the NS of a grease separator?

NS is the nominal size in EN 1825: roughly the flow in litres per second the separator can handle. Standard sizes run 1, 2, 4, 7, 10, 15, 20 and up, and the sludge trap is usually at least 100 litres per NS.