Plumbing Pipe Size Calculator

Add the fixtures a pipe serves to get fixture units and peak flow, then the smallest supply pipe that keeps velocity in limits, its friction loss and pressure left, and the drain, stack and sewer sizes.

يعمل في متصفحك. ملفاتك لا تغادر جهازك أبدًا. شاهد كيف تتحقق

…

كيف تفعل ذلك

  1. 1
    List fixtures

    Add each fixture type and count, or use a quick preset; tick public use if needed.

  2. 2
    Or enter a flow

    Switch to From a known flow and type gpm, L/s or L/min.

  3. 3
    Choose the pipe

    Pick the material and the velocity limit.

  4. 4
    Add the run

    Enter the length, fittings allowance, starting pressure and rise.

  5. 5
    Read the sizes

    See the supply size, velocity, loss, pressure left and the size table.

  6. 6
    Check drains

    Read branch, stack and building drain sizes, then save, export or print.

عن هذه الأداة

A pipe that is too small makes showers weak, taps hiss and water hammer bang; a pipe that is too big costs more and holds cold water longer before the hot arrives. Plumbing codes size pipes from fixture units rather than adding up the full flow of every tap, because not every tap runs at once. This calculator follows that method. In the fixture table add what the pipe serves: bathroom groups, separate toilets with tanks or flush valves, urinals, basins, showers, baths, kitchen sinks, dishwashers, washing machines, laundry trays, service sinks, garden taps, bidets, drinking fountains and floor drains, with how many of each. Quick buttons fill a flat, a family house or a small office toilet block. Tick public use for offices, schools and hotels, which carry higher fixture units. The tool adds the water supply fixture units (WSFU) and turns them into a peak demand in gallons per minute and litres per second with the Hunter curve table, using the flush tank or flush valve column as needed. You can also skip fixtures and type a known flow. Choose the pipe material, from copper type L or M, PEX, CPVC, PVC schedule 40, PPR PN16 or PN20 to galvanised iron, and a velocity limit. The result is the smallest size that keeps the water below that speed, with its inside diameter, the real velocity, the Hazen-Williams friction loss per 100 feet, the loss over your run including an allowance for fittings, and the pressure left at the highest fixture.

Drain, waste and stack sizes

The same fixture list also adds drainage fixture units (DFU). From the IPC tables the tool gives the smallest horizontal fixture branch, the smallest stack with up to three branch intervals and with more, and the building drain or sewer at slopes from 1/16 to 1/2 inch per foot, in inches and millimetres. Any drain that carries a water closet is at least 3 inches (75 mm).

Choosing a velocity limit

Many designers keep cold water below 8 ft/s (2.4 m/s) and hot water below 5 ft/s (1.5 m/s) to limit noise, erosion and water hammer. Lower limits give bigger, quieter pipes. The table under the result shows every size of the chosen material so you can see what one size up or down would do.

Limits

Fixture unit values and tables follow the International Plumbing Code; Uniform Plumbing Code, British, Indian and other national codes use different numbers, so check the code adopted where you build. The tool does not size vents, gas, fire sprinklers or hot water return lines, and it assumes a single pipe run rather than a full network. It is a design aid, not an approval; a licensed plumber or engineer should confirm final sizes.

مثال محلول

A family house has two bathroom groups (3.6 WSFU each), a kitchen sink (1.4), a washing machine (4.0) and a garden tap (2.5), a total of 15.1 WSFU. With flush tanks the Hunter table gives 17.55 gpm (1.11 L/s). In copper type L with an 8 ft/s limit, 3/4 inch would run at 11.6 ft/s, so the pick is 1 inch at 6.8 ft/s with a loss of 8.6 psi per 100 ft. Over 60 ft of pipe plus 50 percent for fittings that is 7.7 psi, and a 6 ft rise costs another 2.6 psi, so 50 psi at the meter leaves about 39.7 psi at the top fixture. The same house has 14 DFU, which needs a 3 inch branch, stack and building drain because toilets are connected.

حقائق سريعة

الأسئلة الشائعة

How do I know what size water pipe I need?

Add up the fixture units of everything the pipe feeds, convert them to a peak flow with the Hunter table, then choose the smallest pipe that keeps the velocity under about 8 ft/s for cold water. The calculator does each step and shows every size of your material so you can compare.

What are fixture units?

They are weights that stand for how much water a fixture uses and how often. A basin in a home is 0.7 water supply fixture units, a toilet with a tank 2.2 and a washing machine 4. Because the scale reflects the chance of fixtures running together, 20 units give far less than 20 times the flow of one unit.

Is PEX sized the same as copper?

No. PEX has thicker walls, so a 3/4 inch PEX pipe has an inside diameter of about 0.67 inch against 0.79 inch for type L copper. At the same flow PEX runs faster, so it often needs the next size up. The tool uses the real inside diameter of each material.

What size drain does a toilet need?

Under the IPC a water closet needs at least a 3 inch (75 mm) drain, and no stack or building drain carrying a toilet may be smaller. Basins can drain through 1.25 to 1.5 inch, showers and kitchen sinks through 1.5 to 2 inch, depending on the code.

How much pressure do I lose in the pipe?

The tool uses the Hazen-Williams formula for the chosen size and material, multiplied by the run length plus a fittings allowance, and adds 0.433 psi for every foot of rise. If less than 15 psi would be left at the highest fixture it warns you to go up a size or add a pump.

Can I use metric units?

Yes. Tick Show metric first to see flows in litres per second and per minute, velocities in metres per second and losses in kPa per 100 m. PPR sizes are listed in millimetres, and drain sizes are given in inches and millimetres.