Junction Box Fill Calculator
Count conductors by AWG size, devices and their yokes, internal clamps, luminaire studs and equipment grounding conductors the way NEC 314.16 does, and see the required volume, the fill of the box you chose with rings and covers, the smallest standard boxes that fit and a printable schedule for every box on the job.
يعمل في متصفحك. ملفاتك لا تغادر جهازك أبدًا. شاهد كيف تتحقق
…
كيف تفعل ذلك
- 1Add a box
Name the box by its location or add several boxes for the whole job.
- 2Count conductors
Enter groups of conductors by AWG size and say whether they enter, pass through or loop.
- 3Add devices
Add each switch or receptacle yoke with the largest conductor connected and the number of gangs.
- 4Add the rest
Enter grounding conductors, studs or hickeys and tick internal clamps if the box has them.
- 5Choose the box
Pick a standard metal box or type a marked volume, add rings or covers and read the fill.
- 6Print the schedule
Print or export the schedule of all boxes with every allowance line for the inspector.
عن هذه الأداة
Overfilled boxes are one of the most common findings on electrical inspections in the United States. NEC 314.16 limits how many conductors and devices a box may hold by comparing two volumes: the volume of the box, plus any marked extension ring, plaster ring or domed cover, and the volume required by its contents. Each item counts as a number of volume allowances taken from Table 314.16(B), which gives 1.50 in³ for 18 AWG, 1.75 for 16 AWG, 2.00 for 14 AWG, 2.25 for 12 AWG, 2.50 for 10 AWG, 3.00 for 8 AWG and 5.00 for 6 AWG. Every conductor that comes from outside the box counts once, and an unbroken conductor that passes through counts once, or twice when the loop is 12 inches or longer. All internal cable clamps together count once, at the size of the largest conductor in the box. Each luminaire stud or hickey counts once. Each yoke or strap holding a device counts twice, at the size of the largest conductor connected to that device, and a device too wide for a single 2-inch gang counts twice for each gang it needs. All equipment grounding conductors and bonding jumpers count once at the size of the largest one, plus a quarter allowance for each beyond four. Pigtails that stay inside the box and up to four small fixture wires from a canopy are not counted. This calculator applies those rules line by line, shows the rule next to every line and totals the required volume. Choose a box from the metal boxes of Table 314.16(A), from 4 inch round boxes to 4-11/16 inch square boxes, device boxes and FS and FD boxes, or type the volume marked on a plastic box, add rings and covers, and see the fill percentage and how much space is left.
Several boxes in one project
A job usually has many boxes. Add each one, name it by location, duplicate similar boxes, and the list shows each fill percentage in green or red. Print the schedule for the inspector or the crew, or export it as CSV.
Editable tables
The allowances and box volumes are those published in the 2023 NEC; the 2020 and 2023 editions use the same values. If your jurisdiction has amended them, change an allowance on the NEC tables tab; the box table then shows the maximum number of conductors of each size, as Table 314.16(A) does.
Not covered
Conductors larger than 6 AWG, which are sized by 314.28 for pull and junction boxes, conduit bodies, the IEC or BS 7671 rules used outside North America, ampacity and derating, and the listing of devices. Plastic boxes must be used at their marked volume, and rings or covers may only be added when they are marked or listed. This is not an official interpretation of the code; the authority having jurisdiction has the final word.
مثال محلول
A kitchen counter box holds two 12/2 cables with ground (four insulated 12 AWG conductors, two grounds), one duplex receptacle and internal clamps. The count is 4 × 2.25 = 9.00 in³ for the conductors, 2.25 for the clamps, 2 × 2.25 = 4.50 for the receptacle yoke and 2.25 for the grounds, 18.00 in³ in total. A 4 × 1-1/2 inch square box gives 21.0 in³, an 86 % fill with 3.00 in³ to spare. Adding a third 12/2 cable raises the requirement to 22.50 in³, so the tool turns red and lists an FD box at 24.0 in³ and a 4-11/16 × 1-1/4 inch square box at 25.5 in³ as the smallest that fit, or a marked plaster ring of at least 1.5 in³ on the original box.
حقائق سريعة
- الفئة: الهندسة والبناء
- يعمل في متصفحك، بلا تسجيل وبلا رفع.
- ما تُدخله يبقى على جهازك.
- متوفر بالإنجليزية.
- آخر مراجعة للمحتوى:
- المصدر الرسمي: NFPA 70, National Electrical Code 2023, section 314.16 and Tables 314.16(A) and 314.16(B)
الأسئلة الشائعة
How do I count the ground wires?
Under 314.16(B)(5) all equipment grounding conductors and bonding jumpers in the box count as one allowance at the size of the largest one. When more than four enter the box, each extra one adds a quarter allowance.
Does a switch or receptacle count as two conductors?
Yes. Each yoke or strap counts as two allowances based on the largest conductor connected to that device. A device wider than a single 2-inch gang counts two allowances for every gang it needs.
Do wire nuts or pigtails count?
No. Wire connectors are not counted, and pigtails that start and end inside the box are not counted either. Only conductors that enter from outside or pass through are counted.
Can I use the volume of a plastic box?
Yes. Choose Custom or marked volume and type the cubic inches stamped inside the box. Non-metallic boxes must be used at their marked volume, not at the metal box table values.
Do extension rings add volume?
Marked extension rings, plaster rings and domed covers add their marked volume to the box. Add each one under Add ring, cover or extension with the number printed on it.
Which NEC edition is used?
The 2023 NEC, whose 314.16 tables match the 2020 edition. Earlier editions counted grounding conductors differently; check the edition adopted where you work and your local amendments.