Electrical Load and Transformer Sizing Calculator

Enter connected load, demand factor, diversity, power factor and growth to choose a standard transformer size with its full-load and fault current, or work out a load factor from energy and peak.

Funziona nel tuo browser. I tuoi file non lasciano mai il dispositivo. Scopri come verificarlo

…

Come si usa

  1. 1
    Choose the calculation

    Transformer or load factor.

  2. 2
    Enter the connected load

    kW.

  3. 3
    Set demand, diversity and PF

    Typical factors.

  4. 4
    Add growth margin

    Percent.

  5. 5
    Read kVA and currents

    Standard size and fault level.

Informazioni su questo strumento

Not every connected load runs at full power at the same time. Electrical designers estimate the maximum demand by applying a demand factor (the share of connected load that actually runs) and a diversity factor (because different loads peak at different times). Dividing by the power factor converts kW into kVA, which is what transformers and generators are rated in. This calculator works out maximum demand, the apparent power with a margin for future growth, the next standard transformer rating, its loading, full-load current and the approximate fault current at its terminals from the impedance voltage. A second mode calculates the load factor from metered energy and peak demand, which shows how evenly a site uses its capacity.

Who this is for

Electrical engineers, building services designers, facility managers, energy managers and students.

Demand and diversity

- **Demand factor:** maximum demand of a group / its connected load, often 0.6-0.9 for commercial loads. - **Diversity factor:** sum of individual maximum demands / maximum demand of the whole, at least 1. Many codes and utility guides tabulate these for dwellings, offices and industry.

Standard transformer ratings (kVA)

25, 50, 100, 160, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600, 2,000, 2,500, 3,150.

Currents

- Full-load current: I = S / (√3 × U). - Prospective short-circuit current at the terminals: Isc ≈ I / uk, where uk is the impedance voltage (typically 4 % for small and 6 % for larger distribution transformers). The supply network's impedance lowers it in practice.

Worked example

400 kW connected with a demand factor of 0.8 and power factor 0.9 gives 320 kW and 356 kVA. With 20 % growth, 427 kVA is needed, so a 500 kVA transformer, loaded at 71 %. At 400 V, its full-load current is 722 A and the fault current about 12 kA with uk = 6 %.

Load factor

Load factor = energy / (peak demand × hours). 36,000 kWh in a 720-hour month with a 120 kW peak is 41.7 %. A low load factor means expensive peak capacity is used only briefly; peak shaving and load shifting can reduce demand charges.

Power factor

Low power factor raises kVA and current for the same kW. Correcting from 0.8 to 0.95 reduces the kVA by 16 %, which can avoid a transformer upgrade.

Common mistakes

- Adding nameplate ratings without demand factors, which oversizes the transformer and raises no-load losses. - Forgetting to convert kW to kVA, which undersizes it when power factor is poor. - Leaving no margin for future load, so the next extension needs a second transformer. - Using the transformer full-load current to size the main breaker without checking the switchgear fault rating. - Treating diversity as a fixed number: it rises with the number of independent loads, so small groups need values close to 1. Transformers run most efficiently at roughly 40-60 % load, which is one reason designers avoid sizing exactly to peak demand.

Limits

Simplified demand estimate; harmonics, motor starting and unbalanced loads need further checks. This is not professional engineering advice.

Esempio svolto

400 kW connected, DF 0.8, PF 0.9, +20 %: 500 kVA transformer, 722 A at 400 V.

In breve

Domande frequenti

What is a demand factor?

The ratio of maximum demand to connected load.

Why are transformers rated in kVA?

Their heating depends on current, whatever the power factor.

How do I find the full-load current?

kVA × 1,000 / (√3 × voltage).

What is uk?

The impedance voltage in percent, which limits fault current.

What is a good load factor?

Higher is better; 60-80 % is good for many commercial sites.

Is my data stored?

Nothing leaves your browser.