Sprinkler K-Factor and Density-Area Calculator
Work out head flow from pressure with Q = K√P, or the sprinkler demand, heads in the design area, pressure at a head and water volume by NFPA 13 or EN 12845 hazard class.
Läuft in Ihrem Browser. Ihre Dateien verlassen nie Ihr Gerät. So prüfen Sie es
…
So geht's
- 1Choose the method
K-factor, NFPA 13 or EN 12845.
- 2Pick the hazard class
Light, ordinary or extra/high.
- 3Enter the head K-factor
And coverage per head.
- 4Read head flow and pressure
At the remote head.
- 5Read the demand
Flow, duration and water volume.
Über dieses Tool
Automatic sprinklers are sized by hazard. Each standard sets a design density, the water discharge in mm/min or gpm/ft², over a design area where sprinklers are assumed to open. Each sprinkler's flow follows from its K-factor and the pressure at the head: Q = K·√P. The total demand is the density times the area plus an allowance for fire service hose streams, and the water supply must sustain it for a set duration. This calculator gives head flow and pressure from the K-factor, and preliminary demand figures for NFPA 13 hazard classes and EN 12845 hazard groups, including the number of heads in the design area, the pressure needed at the most remote head and the water volume to store.
Who this is for
Fire protection engineers, sprinkler designers and contractors, building services engineers, insurers and students.
K-factor
Q = K·√P. Common K-factors: K80 (metric, L/min/bar^½, equal to K5.6 US) and K115 (K8.0). A K80 head at 1 bar discharges 80 L/min. Minimum operating pressures: 0.5 bar in EN 12845, 7 psi in NFPA 13.
NFPA 13 density/area (classic points)
| Hazard | Density | Area | Hose | Duration | |---|---|---|---|---| | Light | 0.10 gpm/ft² | 1,500 ft² | 100 gpm | 30 min | | Ordinary 1 | 0.15 | 1,500 | 250 | 60-90 | | Ordinary 2 | 0.20 | 1,500 | 250 | 60-90 | | Extra 1 | 0.30 | 2,500 | 500 | 90-120 | | Extra 2 | 0.40 | 2,500 | 500 | 90-120 |
EN 12845 (Table 3)
| Group | Density | Area | Duration | |---|---|---|---| | LH | 2.25 mm/min | 84 m² | 30 min | | OH1-OH4 | 5.0 mm/min | 72, 144, 216, 360 m² | 60 min | | HHP1-HHP3 | 7.5, 10, 12.5 mm/min | 260 m² | 90 min | (1 mm/min = 1 L/min per m².)
Worked example
NFPA 13 Ordinary Hazard Group 1 with K5.6 heads at 130 ft² each: 12 heads in the 1,500 ft² area, 19.5 gpm per head at 12.1 psi, sprinkler demand 225 gpm plus 250 gpm hose allowance, 475 gpm for 60 minutes, about 108 m³ of water.
EN example
OH1 with K80 heads at 12 m² each: 60 L/min per head at 0.56 bar, 360 L/min over 72 m² and 21.6 m³ for 60 minutes.
From preliminary to final
These are starting values. Final design needs full hydraulic calculations (Hazen-Williams friction through the piping to the most remote area), pump or supply curves and the latest edition of the standard.
Example uses
A designer makes a first estimate of the water tank for an ordinary hazard warehouse.
Limits
Preliminary sizing only; storage, in-rack and special hazard design are excluded. This is not professional engineering advice.
Rechenbeispiel
NFPA OH1: 0.15 gpm/ft² × 1,500 ft² = 225 gpm plus 250 gpm hose, 12.1 psi at a K5.6 head.
Kurzinfos
- Kategorie: Technik & Bau
- Läuft in Ihrem Browser, ohne Anmeldung, ohne Upload.
- Ihre Eingaben bleiben auf Ihrem Gerät.
- Auf Englisch verfügbar.
- Inhalt zuletzt geprüft:
- Offizielle Quelle: Sprinkler hydraulics Q = K·√P; NFPA 13 density/area points with hose allowances and durations; EN 12845 design densities and areas of operation (Table 3)
Häufig gestellte Fragen
What is a sprinkler K-factor?
The constant in Q = K·√P linking flow and pressure.
What density does light hazard need?
0.10 gpm/ft² in NFPA 13, 2.25 mm/min in EN 12845.
What is the design area?
The area over which sprinklers are assumed to operate at once.
Why add a hose allowance?
Fire services use the same supply for hose streams.
Is this a full hydraulic calculation?
No. It gives preliminary demand values.
Is my data stored?
No. Design values stay on your computer.