Sprinkler K-Factor and Density-Area Calculator

Work out head flow from pressure with Q = K√P, or the sprinkler demand, heads in the design area, pressure at a head and water volume by NFPA 13 or EN 12845 hazard class.

S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho

…

Com es fa

  1. 1
    Choose the method

    K-factor, NFPA 13 or EN 12845.

  2. 2
    Pick the hazard class

    Light, ordinary or extra/high.

  3. 3
    Enter the head K-factor

    And coverage per head.

  4. 4
    Read head flow and pressure

    At the remote head.

  5. 5
    Read the demand

    Flow, duration and water volume.

Sobre aquesta eina

Automatic sprinklers are sized by hazard. Each standard sets a design density, the water discharge in mm/min or gpm/ft², over a design area where sprinklers are assumed to open. Each sprinkler's flow follows from its K-factor and the pressure at the head: Q = K·√P. The total demand is the density times the area plus an allowance for fire service hose streams, and the water supply must sustain it for a set duration. This calculator gives head flow and pressure from the K-factor, and preliminary demand figures for NFPA 13 hazard classes and EN 12845 hazard groups, including the number of heads in the design area, the pressure needed at the most remote head and the water volume to store.

Who this is for

Fire protection engineers, sprinkler designers and contractors, building services engineers, insurers and students.

K-factor

Q = K·√P. Common K-factors: K80 (metric, L/min/bar^½, equal to K5.6 US) and K115 (K8.0). A K80 head at 1 bar discharges 80 L/min. Minimum operating pressures: 0.5 bar in EN 12845, 7 psi in NFPA 13.

NFPA 13 density/area (classic points)

| Hazard | Density | Area | Hose | Duration | |---|---|---|---|---| | Light | 0.10 gpm/ft² | 1,500 ft² | 100 gpm | 30 min | | Ordinary 1 | 0.15 | 1,500 | 250 | 60-90 | | Ordinary 2 | 0.20 | 1,500 | 250 | 60-90 | | Extra 1 | 0.30 | 2,500 | 500 | 90-120 | | Extra 2 | 0.40 | 2,500 | 500 | 90-120 |

EN 12845 (Table 3)

| Group | Density | Area | Duration | |---|---|---|---| | LH | 2.25 mm/min | 84 m² | 30 min | | OH1-OH4 | 5.0 mm/min | 72, 144, 216, 360 m² | 60 min | | HHP1-HHP3 | 7.5, 10, 12.5 mm/min | 260 m² | 90 min | (1 mm/min = 1 L/min per m².)

Worked example

NFPA 13 Ordinary Hazard Group 1 with K5.6 heads at 130 ft² each: 12 heads in the 1,500 ft² area, 19.5 gpm per head at 12.1 psi, sprinkler demand 225 gpm plus 250 gpm hose allowance, 475 gpm for 60 minutes, about 108 m³ of water.

EN example

OH1 with K80 heads at 12 m² each: 60 L/min per head at 0.56 bar, 360 L/min over 72 m² and 21.6 m³ for 60 minutes.

From preliminary to final

These are starting values. Final design needs full hydraulic calculations (Hazen-Williams friction through the piping to the most remote area), pump or supply curves and the latest edition of the standard.

Example uses

A designer makes a first estimate of the water tank for an ordinary hazard warehouse.

Limits

Preliminary sizing only; storage, in-rack and special hazard design are excluded. This is not professional engineering advice.

Exemple resolt

NFPA OH1: 0.15 gpm/ft² × 1,500 ft² = 225 gpm plus 250 gpm hose, 12.1 psi at a K5.6 head.

En resum

Preguntes freqüents

What is a sprinkler K-factor?

The constant in Q = K·√P linking flow and pressure.

What density does light hazard need?

0.10 gpm/ft² in NFPA 13, 2.25 mm/min in EN 12845.

What is the design area?

The area over which sprinklers are assumed to operate at once.

Why add a hose allowance?

Fire services use the same supply for hose streams.

Is this a full hydraulic calculation?

No. It gives preliminary demand values.

Is my data stored?

No. Design values stay on your computer.

Totalment gratisSense cost, sense registre
Els fitxers es mantenen privatsTot funciona al teu navegador
Fàcil en el teu idiomaDisponible en molts idiomes