NEC Residential Electrical Load Calculation (Article 220)
Enter floor area, small-appliance and laundry circuits and each appliance and HVAC load, and see the standard and optional method totals in VA, the amps at 240 V and the next standard service size.
S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho
…
Com es fa
- 1Choose the method
Standard or optional for the headline.
- 2Enter the area
Square feet of living space.
- 3Set circuits
Small-appliance and laundry counts.
- 4List loads
Appliances and HVAC with nameplate VA.
- 5Read both totals
VA, amps and service size.
- 6Export
CSV or print for the permit file.
Sobre aquesta eina
Before a new service is installed or an old one is upgraded for a heat pump, an EV charger or a kitchen remodel, the electrician and the inspector want a load calculation that follows Article 220 of the National Electrical Code. The calculation is not hard, but it has many small rules that are easy to forget: the 3 volt-amperes per square foot for general lighting, the two small-appliance circuits and the laundry circuit at 1,500 VA each, the demand factors that take the first 3,000 VA at 100% and the next block at 35%, the 75% factor for four or more fixed appliances, the 5,000 VA minimum for a dryer, Column C of Table 220.55 for ranges and the rule that heating and cooling are not added together. This calculator follows the 2023 edition and runs both of the methods the code allows for a single-family dwelling. In the standard method of Part III each group of loads gets its own demand factor. In the optional method of 220.82 all general loads and appliance nameplates are added, the first 10 kVA counts in full and the rest at 40%, and heating or air conditioning is added according to 220.82(C). You enter the floor area, the number of small-appliance and laundry circuits, the service voltage and a table of appliances and HVAC equipment with their nameplate VA and type. The tool shows both totals line by line, the current at 240 V and the next standard rating from 240.6(A), never below 100 A.
Who this is for
Electricians preparing a permit application, homeowners planning a panel upgrade, energy auditors checking whether a heat pump or EV charger fits on an existing service, and electrical students learning the steps of Article 220.
Floor area and general lighting
Use the outside dimensions of the dwelling, without open porches, garages or unfinished spaces that cannot be adapted for living. Since the 2020 edition the general lighting load for dwellings is 3 VA per square foot in Table 220.12.
Fixed appliances
Dishwashers, disposals, water heaters, built-in microwaves and similar fastened-in-place loads go in as fixed appliances. With four or more of them the total is taken at 75% under 220.53. Ranges, dryers, space heating and air conditioning are handled separately.
Ranges and dryers
A single range up to 12 kW counts as 8 kW from Column C of Table 220.55; above 12 kW the figure rises 5% for each extra kW. A dryer counts as 5,000 VA or its nameplate, whichever is larger.
Heating and cooling
Heating and air conditioning do not run at the same time, so 220.60 lets you use the larger of the two. A heat pump compressor counts on both sides. The optional field for 25% of the largest motor covers the motor rule when it applies.
Choosing a method
The optional method often gives a smaller service for homes with many appliances, because of its 40% factor above 10 kVA. It applies to a dwelling unit served by a single 120/240 V or 208Y/120 V service of 100 A or more.
Limits
A planning aid based on NEC 2023, not a design or approval. Your state or city may use another edition and local amendments, and the authority having jurisdiction and the utility decide. Conductor, panel, grounding and EV load management checks are separate; a licensed electrician must design the installation.
Exemple resolt
The default dwelling has 2,400 sq ft, two small-appliance circuits and one laundry circuit, a dishwasher, disposal, 4,500 VA water heater and built-in microwave, a 5,000 VA dryer, a 12 kW range, 10 kW of baseboard heat and a 5,000 VA air conditioner. The standard method gives 35,120 VA, or 146.3 A at 240 V, so a 150 A service. The optional method gives 27,220 VA, or 113.4 A, so 125 A.
En resum
- Categoria: Enginyeria i construcció
- S'executa al navegador, sense registre, sense pujar res.
- La informació que introdueixes es queda al dispositiu.
- Disponible en anglès.
- Contingut revisat per última vegada:
- Font oficial: NFPA 70 National Electrical Code 2023, Article 220
Preguntes freqüents
Which NEC edition does this use?
The 2023 edition. Check which edition and amendments your jurisdiction has adopted.
Why is the general lighting load 3 VA per square foot?
That is the unit load for dwelling units in Table 220.12 of recent editions.
Do I add heating and air conditioning together?
No. They are noncoincident loads, so the larger one is used.
Can I use the optional method for an existing house?
Yes, 220.83 covers additions to existing dwellings; this tool applies 220.82 for the whole dwelling.
Does the tool size the service conductors?
No. It gives the calculated load and service rating; conductor sizing is a separate step.
What about an EV charger?
Add it as a fixed appliance at its nameplate rating, or as a continuous load as your inspector requires.