Lighting Calculator: Lumen Method Luminaire Count

Enter room size, mounting height, target lux, luminaire lumens and wattage, utilisation and maintenance factors to get the number of fittings, a layout grid, the achieved illuminance and the lighting power density.

S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho

…

Com es fa

  1. 1
    Enter the room

    Length, width, mounting height.

  2. 2
    Set the target

    Maintained lux.

  3. 3
    Enter the luminaire

    Lumens and watts.

  4. 4
    Set UF and MF

    From manufacturer data.

  5. 5
    Read fittings and layout

    Grid, lux, W/m².

Sobre aquesta eina

The lumen method is the standard hand calculation for general lighting. It asks how much light must land on the working plane, the target illuminance times the floor area, and divides by the useful light each fitting delivers: its lamp lumens times a utilisation factor (the share that reaches the working plane after the room's surfaces absorb some) and a maintenance factor (the loss from dirt and ageing before cleaning or replacement). This calculator rounds the result up to whole fittings, suggests a grid that fits the room, checks the spacing to mounting height ratio for uniformity and reports power density, the figure energy codes limit.

Who this is for

Electrical and lighting designers, electricians, facility managers, architects and students.

Target illuminance (EN 12464-1)

| Space | Maintained lux | |---|---| | Corridors | 100 | | Stairs, storage | 100-200 | | Canteens, reception | 200-300 | | Offices, classrooms (writing, reading) | 500 | | Technical drawing, fine assembly | 750 | | Precision work, inspection | 1,000-1,500 |

Room index and utilisation factor

K = L × W / (Hm × (L + W)), where Hm is the luminaire height above the working plane (usually 0.75-0.85 m above floor). Low K (narrow, tall rooms) means more light hits the walls, so UF is lower. Manufacturers publish UF tables by room index and surface reflectances; 0.5-0.7 is typical for modern LED fittings in offices.

Maintenance factor

MF = lumen maintenance × luminaire maintenance × room surface maintenance. Clean offices with LEDs often use 0.8; dirty industrial spaces 0.6-0.7.

Spacing

Keep the spacing to height ratio (SHR) below the manufacturer's maximum, often 1.0-1.5, so the floor is evenly lit. Fittings near walls are usually half a spacing from the wall.

Worked example

A 10 × 8 m office at 500 lx, fittings of 4,000 lm and 32 W, UF 0.6, MF 0.8, Hm 2.2 m: room index 2.02 and 20.8 fittings, so 21 in a 7 × 3 grid giving 504 lx, 672 W and 8.4 W/m² (1.67 W/m² per 100 lx).

Power density

Energy codes cap lighting power density; offices are typically limited to 6-10 W/m². LED fittings with 120-150 lm/W make 500 lx achievable at under 7 W/m².

Common mistakes

- Using the lamp lumens of an LED chip instead of the luminaire output, which overstates the light delivered. - Forgetting the maintenance factor, so the room meets the target only on the first day. - Measuring illuminance at floor level instead of the working plane. - Spacing fittings too widely, giving bright patches under the fittings and dark areas between. - Ignoring daylight controls, which can cut lighting energy by a third in perimeter zones.

Limits

Average illuminance only; uniformity, glare (UGR) and task lighting need point-by-point software such as DIALux or Relux. This is not professional engineering advice.

Exemple resolt

10 × 8 m office, 500 lx, 4,000 lm fittings: 21 luminaires, 504 lx, 8.4 W/m².

En resum

Preguntes freqüents

How many lights do I need?

N = lux × area / (lumens × UF × MF).

What is the utilisation factor?

The share of lamp lumens reaching the working plane.

What maintenance factor should I use?

Around 0.8 for clean spaces with LEDs.

How much light does an office need?

500 lx maintained on the desk by EN 12464-1.

What is the room index?

L × W / (Hm × (L + W)), used to read UF tables.

Is my data stored?

No. Room inputs are not sent anywhere.