Fire Alarm Zone and Detector Planner (BS 5839-1)

Enter floor areas and storeys to get the number of detection zones under BS 5839-1, or a room's length and width to estimate how many point smoke or heat detectors it needs.

S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho

…

Com es fa

  1. 1
    Choose zones or room

    Mode.

  2. 2
    Enter floor areas

    And storeys.

  3. 3
    Check the search distance

    Under 60 m.

  4. 4
    Enter room size

    For detector counts.

  5. 5
    Choose detector type

    Smoke or heat.

Sobre aquesta eina

Fire alarm systems divide a building into detection zones so that responders can find a fire quickly from the control panel. BS 5839-1, the UK code of practice for non-domestic premises, limits each zone to 2,000 m² of floor area and the search distance within a zone to 60 m, and normally confines a zone to one storey unless the whole building is no larger than 300 m². Within each room, point detectors must cover every part of the ceiling: no point may be more than 7.5 m horizontally from a smoke detector or 5.3 m from a heat detector. This calculator gives the minimum number of zones per storey and in total, and estimates detector numbers for a rectangular room on a square grid.

Who this is for

Fire alarm designers and installers, building services engineers, fire risk assessors, facility managers and students.

Zoning rules (BS 5839-1)

- Floor area of a zone: no more than 2,000 m². - Search distance (to see the location of a fire within the zone): no more than 60 m. - A zone should not cover more than one storey, unless the total floor area of the building is 300 m² or less. - Stairwells, lift shafts and similar vertical structures are usually separate zones. - Where addressable systems identify each device, zones still help responders plan.

Detector coverage

- Smoke detectors: every point within 7.5 m horizontally. - Heat detectors: within 5.3 m. On a square grid, the maximum spacing is r·√2: 10.6 m for smoke, 7.5 m for heat, each detector covering about 112 m² and 56 m² respectively. Corridors under 2 m wide allow longer spacing along the corridor. Sloping ceilings, beams, voids and ceiling height (smoke up to about 10.5 m, heat up to 9 m for typical grades) change these rules.

Worked example

A three-storey building of 4,500 m² per floor needs at least three zones per floor, nine in total. A 20 × 15 m room needs four smoke detectors on a 10.6 m grid, one per 75 m².

System categories

BS 5839-1 categories range from M (manual call points only) through L1-L5 (life protection) to P1-P2 (property protection). The category decides where detectors are required.

Example uses

A designer splits a large warehouse floor into zones. A fire risk assessor checks whether an existing panel's zones meet BS 5839-1. An installer estimates detector numbers for a quote.

Manual call points

Call points are placed on exits to storeys and to open air, so that nobody walks more than 45 m to one (25 m in some higher-risk areas).

Limits

Simplified rectangular layouts; obstructions, ceiling shape and specific product data change spacing. Designs must be checked by a competent person. This is not professional fire safety advice.

Exemple resolt

4,500 m² per floor, 3 storeys: at least 9 zones; a 20 × 15 m room needs 4 smoke detectors.

En resum

Preguntes freqüents

How big can a fire alarm zone be?

No more than 2,000 m² under BS 5839-1.

What is the search distance?

The walking distance to find a fire within a zone, no more than 60 m.

Can one zone cover several floors?

Only if the whole building is 300 m² or less.

How far apart can smoke detectors be?

About 10.6 m on a square grid, so no point is over 7.5 m from a detector.

Does this replace a design?

No. It gives preliminary quantities.