Fire Alarm Zone and Detector Planner (BS 5839-1)
Enter floor areas and storeys to get the number of detection zones under BS 5839-1, or a room's length and width to estimate how many point smoke or heat detectors it needs.
S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho
…
Com es fa
- 1Choose zones or room
Mode.
- 2Enter floor areas
And storeys.
- 3Check the search distance
Under 60 m.
- 4Enter room size
For detector counts.
- 5Choose detector type
Smoke or heat.
Sobre aquesta eina
Fire alarm systems divide a building into detection zones so that responders can find a fire quickly from the control panel. BS 5839-1, the UK code of practice for non-domestic premises, limits each zone to 2,000 m² of floor area and the search distance within a zone to 60 m, and normally confines a zone to one storey unless the whole building is no larger than 300 m². Within each room, point detectors must cover every part of the ceiling: no point may be more than 7.5 m horizontally from a smoke detector or 5.3 m from a heat detector. This calculator gives the minimum number of zones per storey and in total, and estimates detector numbers for a rectangular room on a square grid.
Who this is for
Fire alarm designers and installers, building services engineers, fire risk assessors, facility managers and students.
Zoning rules (BS 5839-1)
- Floor area of a zone: no more than 2,000 m². - Search distance (to see the location of a fire within the zone): no more than 60 m. - A zone should not cover more than one storey, unless the total floor area of the building is 300 m² or less. - Stairwells, lift shafts and similar vertical structures are usually separate zones. - Where addressable systems identify each device, zones still help responders plan.
Detector coverage
- Smoke detectors: every point within 7.5 m horizontally. - Heat detectors: within 5.3 m. On a square grid, the maximum spacing is r·√2: 10.6 m for smoke, 7.5 m for heat, each detector covering about 112 m² and 56 m² respectively. Corridors under 2 m wide allow longer spacing along the corridor. Sloping ceilings, beams, voids and ceiling height (smoke up to about 10.5 m, heat up to 9 m for typical grades) change these rules.
Worked example
A three-storey building of 4,500 m² per floor needs at least three zones per floor, nine in total. A 20 × 15 m room needs four smoke detectors on a 10.6 m grid, one per 75 m².
System categories
BS 5839-1 categories range from M (manual call points only) through L1-L5 (life protection) to P1-P2 (property protection). The category decides where detectors are required.
Example uses
A designer splits a large warehouse floor into zones. A fire risk assessor checks whether an existing panel's zones meet BS 5839-1. An installer estimates detector numbers for a quote.
Manual call points
Call points are placed on exits to storeys and to open air, so that nobody walks more than 45 m to one (25 m in some higher-risk areas).
Limits
Simplified rectangular layouts; obstructions, ceiling shape and specific product data change spacing. Designs must be checked by a competent person. This is not professional fire safety advice.
Exemple resolt
4,500 m² per floor, 3 storeys: at least 9 zones; a 20 × 15 m room needs 4 smoke detectors.
En resum
- Categoria: Enginyeria i construcció
- S'executa al navegador, sense registre, sense pujar res.
- La informació que introdueixes es queda al dispositiu.
- Disponible en anglès.
- Contingut revisat per última vegada:
- Font oficial: BS 5839-1:2017 fire detection and alarm systems: zone area up to 2,000 m², search distance up to 60 m, single zone for buildings up to 300 m²; point detector coverage radius 7.5 m (smoke) and 5.3 m (heat) under flat ceilings
Preguntes freqüents
How big can a fire alarm zone be?
No more than 2,000 m² under BS 5839-1.
What is the search distance?
The walking distance to find a fire within a zone, no more than 60 m.
Can one zone cover several floors?
Only if the whole building is 300 m² or less.
How far apart can smoke detectors be?
About 10.6 m on a square grid, so no point is over 7.5 m from a detector.
Does this replace a design?
No. It gives preliminary quantities.
Is my data stored?
No. Building data stays in this browser.