Earth Electrode and Ground Rod Resistance Calculator
Estimate the resistance to earth of driven rods, plates and buried strips from measured soil resistivity, combine several rods with the screening factor from your standard, see how long a single rod must be to reach your target, turn Wenner four-pin readings into resistivity, and keep a log of fall-of-potential test results against your target.
S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho
…
Com es fa
- 1Enter soil data
Type the measured soil resistivity and a seasonal factor for dry or frozen ground.
- 2Choose the electrode
Select rods, a plate or a strip and enter length, diameter, area, width and depth.
- 3Add more rods
Set the number of rods and spacing, then type the screening factor λ from your standard.
- 4Set a target
Enter the required resistance and read whether the design reaches it or shows incomplete.
- 5Measure the soil
Enter Wenner readings to get resistivity at each depth and use the average in the design.
- 6Log the tests
Record installed electrode tests, check the 62 percent plateau and print or export the log.
Sobre aquesta eina
The resistance between an earth electrode and the surrounding soil decides how well a fault current or a surge is carried away, and specifications usually set a limit. In the United States NEC 250.53(A)(2) asks for a supplemental electrode when a single rod, pipe or plate electrode measures more than 25 ohms; telecom, data centre and lightning specifications often set their own lower targets, and TT installations need a value low enough for the residual current device to operate. The single most important input is soil resistivity, which can differ by a factor of a thousand between wet clay and dry sand or rock and changes with moisture and frost. This calculator uses closed-form formulas for uniform soil and builds in no tables. A driven rod follows Dwight's equation R = ρ / (2πL) × (ln(8L/d) − 1), so doubling the length roughly halves the resistance while a thicker rod helps very little. A plate is treated as a flat disc of the same area lying on the soil surface, R = ρ / (4a) with a = √(A/π), the exact result for a disc on a uniform half-space, which is on the safe side for a buried plate. A horizontal strip or bare conductor uses Dwight's formula for a buried horizontal wire, with the width of a flat strip turned into an equivalent radius. Rods in parallel do not divide the resistance by their number, because each sits in the voltage field of the others; the tool applies R = R1 (1 + λα) / n with α = ρ / (2π R1 s), and you type the screening factor λ from the table in the standard you design to, such as BS 7430 or IEEE Std 142, for your number of rods, layout and spacing. A seasonal factor lets you design for dry or frozen soil. Set a target and the tool says whether the design reaches it and how long a single rod would have to be. The soil tab turns Wenner readings into resistivity for each probe spacing and passes the average to the design.
What is built in and what you enter
Built in: the Dwight rod and horizontal wire formulas, the half-space disc result, the parallel-rod expression, the Wenner formula with and without pin depth and the NEC length and 25 ohm references. Entered by you: soil resistivity, the seasonal factor, the target, and every screening factor λ. No screening-factor or soil-resistivity table ships with the tool, because we could not confirm those values from a free published source. While a required value is missing the result reads "incomplete: enter values from the standard" and no pass state is shown.
Test log
Record each measurement with date, electrode, method (fall of potential with the 62 percent rule, three-point, clamp-on, two-point or slope), reading, soil condition, temperature, tester and notes. The status compares each reading with your target, and shows incomplete when no target is set. A fall-of-potential helper interpolates the value at 62 percent of the distance and checks the plateau between 52 and 72 percent; a spread above about 10 percent means the current probe is too close.
Limits and safety
The formulas assume uniform soil. In layered soil, near buried metal or for substations where touch and step voltages matter (IEEE 80, EN 50522), results can be far off and a soil model with design software is needed. Concrete-encased electrodes, ground rings and chemical rods are not modelled separately. Estimates do not replace measurement: always test the installed electrode. Verify with a qualified engineer.
Exemple resolt
A farm building needs 25 ohms or less. Wenner readings at 1, 2, 4 and 8 m spacing give 18.2, 8.6, 4.1 and 2.2 ohms, which with 0.2 m pin depth work out to about 122, 110, 104 and 111 ohm-metres, so below the top metre the soil is fairly uniform at roughly 110 ohm-metres. Designing with 100 ohm-metres, one 2.4 m rod of 16 mm diameter gives 40.4 ohms, above the target, and a single rod would need to be about 4.2 m long. For two rods 4.8 m apart the result stays incomplete until the engineer types the screening factor from the BS 7430 table; with λ = 1.00 entered the pair gives about 21.9 ohms. The fall-of-potential test on the first rod alone reads 25.1 ohms at 62 percent with a 5 percent plateau spread, logged as above target until the second rod is bonded in.
En resum
- Categoria: Enginyeria i construcció
- S'executa al navegador, sense registre, sense pujar res.
- La informació que introdueixes es queda al dispositiu.
- Disponible en anglès.
- Contingut revisat per última vegada:
- Font oficial: H. B. Dwight, Calculation of Resistances to Ground (AIEE Transactions, 1936), as reproduced in IEEE Std 142-2007 chapter 4; Wenner (1915) four-electrode method; NEC 250.52(A)(5) and 250.53(A)(2)
Preguntes freqüents
What resistance should a ground rod have?
It depends on the rule that applies. NEC 250.53(A)(2) lets a single rod stand alone at 25 ohms or less and otherwise requires a supplemental electrode; telecom, data and lightning systems often specify lower values. Enter the target your specification sets.
Why do I have to type the screening factor?
Rods close together share the same soil, so their combined resistance depends on a factor that the standards tabulate by number of rods, layout and spacing. We could not confirm those tables from a free source, so you enter λ from your copy of BS 7430, IEEE Std 142 or your design guide.
Where do I get soil resistivity?
Measure it with a four-pin Wenner test and enter the readings on the soil tab, or use a value from a geotechnical survey of the site. The tool does not guess it from a soil description.
What is the seasonal factor?
Soil resistivity can rise several times when the ground dries out or freezes. Multiply by a factor you choose for your climate to design for the worst season instead of the day you measured.
What is the 62 percent rule?
In the fall-of-potential test the potential probe is placed at 62 percent of the distance to the current probe, where the reading equals the electrode resistance in uniform soil. Readings at 52 and 72 percent should agree within about 10 percent.
Can I use this for a substation grid?
No. Substation grounding must also control touch and step voltages and is designed with IEEE 80 or EN 50522 and layered soil models. This tool is for rods, plates and strips in ordinary installations.