4-20 mA Signal Scaling Calculator
Convert a loop current or voltage to process units and back for any range, check that the loop supply is enough, and record as-found and as-left calibration readings.
S'executa al teu navegador. Els fitxers mai no surten del dispositiu. Mira com comprovar-ho
…
Com es fa
- 1Set the range
Enter tag, signal type, lower and upper range values and the unit.
- 2Choose the characteristic
Pick linear or square root, and a low-flow cut-off if needed.
- 3Convert
Type a signal to get the value, or a value to get the signal.
- 4Check the loop
On Loop check enter supply, transmitter minimum, loads and cable.
- 5Record calibration
On Calibration table type as-found and as-left readings at each point.
- 6Print the loop sheet
Press Report, or CSV for the readings.
Sobre aquesta eina
The 4-20 mA current loop is still the backbone of process instrumentation. A transmitter turns pressure, level, flow or temperature into a current between 4 and 20 mA, and a controller or PLC turns it back into engineering units. Using a live zero at 4 mA means a broken wire reads 0 mA and is easy to tell apart from a real zero. Technicians do this scaling constantly: what should the PLC show at 12 mA, what current should a pressure of 6.5 bar give, is the loop drawing enough voltage for the transmitter at full scale? This calculator handles any lower and upper range value, including inverted and negative ranges, and the common voltage signals 0-10 V, 1-5 V, 0-5 V and 2-10 V, as well as 0-20 mA. For differential pressure flowmeters it applies square-root extraction with a low-flow cut-off. It interprets the current against the NAMUR NE 43 bands so fault signals are recognised, checks the voltage left at a two-wire transmitter after the loop loads and cable, and produces a five-point or nine-point calibration sheet with errors in percent of span.
Scaling
The value is LRV + (signal − signal low) / signal span × (URV − LRV). For 4-20 mA the signal span is 16 mA, so 12 mA is always 50 %. With square root selected, the fraction is square-rooted, which is how flow is derived from differential pressure in ISO 5167 orifice and venturi meters; at 8 mA, a quarter of the signal span, the flow is half of full scale. Below the cut-off the flow is forced to zero, because the square root greatly amplifies noise near zero. The curve and quick-point table show the whole range at once.
NAMUR NE 43
NE 43 lets a transmitter signal its own failure. Currents from 3.8 to 20.5 mA are valid measurements, with 3.8 to 4 and 20 to 20.5 showing under- and over-range. At or below 3.6 mA, or at or above 21 mA, the transmitter reports a fault. The tile labels the current you typed so you can configure alarms consistently.
Loop check
A two-wire transmitter needs a minimum voltage at its terminals, often 10.5 to 12 V. Every load in the loop, such as the PLC input resistor, an indicator or a HART resistor, plus both cable cores, drops voltage. Enter the loads, cable resistance and length, and the highest current, ideally 22 mA so that alarm currents still work. The tool shows the voltage left and the spare resistance.
Calibration sheet
List test points, type as-found and as-left readings and set the tolerance in percent of span. Errors are shown in red when outside tolerance. The up-down button creates a nine-point check for hysteresis. Report prints a loop sheet with signature lines.
Limits
Not a substitute for a licensed engineer's loop design or a calibration procedure. The tool does not model HART communication, intrinsic safety barriers or transmitter damping. Use a calibrated reference instrument for real readings.
Exemple resolt
A pressure transmitter is ranged 0 to 10 bar on 4-20 mA. A reading of 12 mA is 50 % of span, 5.000 bar; a pressure of 6.5 bar should give 4 + 0.65 × 16 = 14.40 mA. The loop runs on 24 V through a 250 Ω PLC input and 300 m of 0.5 mm² cable at 36 Ω/km, adding 21.6 Ω, so the total is 271.6 Ω. At 22 mA the transmitter sees 24 − 0.022 × 271.6 = 18.0 V, well above its 12 V minimum, and the loop could take up to 273 Ω more. At the 50 % calibration point an as-found reading of 12.05 mA is 0.31 % of span off, outside a 0.25 % tolerance; after adjustment it reads 12.00 mA and passes.
En resum
- Categoria: Enginyeria i construcció
- S'executa al navegador, sense registre, sense pujar res.
- La informació que introdueixes es queda al dispositiu.
- Disponible en anglès.
- Contingut revisat per última vegada:
- Font oficial: IEC 60381-1 and -2; NAMUR NE 43
Preguntes freqüents
Why does the signal start at 4 mA and not 0?
A live zero lets the receiver tell a real zero from a broken wire or dead transmitter, and leaves enough current to power a two-wire transmitter at the bottom of its range.
How do I scale a reversed range?
Enter the value at 4 mA as the lower range value and the value at 20 mA as the upper, even if it is smaller. The formula works either way, so a level that falls as current rises scales correctly.
When should I use square-root extraction?
Only when the transmitter measures differential pressure across a flow element and is not doing the square root itself. If the transmitter or the DCS already extracts it, applying it again gives wrong flow.
What load resistance can my loop take?
Subtract the transmitter minimum voltage from the supply and divide by the highest current. With 24 V, a 12 V minimum and 22 mA, the maximum is about 545 Ω including cable.
Does it work for 0-10 V signals?
Yes. Choose 0-10 V, 1-5 V, 0-5 V or 2-10 V from the signal list. The NE 43 status applies only to 4-20 mA.
Can I keep calibration records here?
Readings are saved in this browser and in a JSON backup. For formal records, print the report or export the CSV into your maintenance system.