Conduit Fill Calculator (NEC 40% Rule)
Check conduit fill for THHN wires and find the smallest EMT size that meets the NEC limit.
Runs in your browser. Your files never leave your device. See how to check
…
How to do it
- 1Step 1: Open Conduit Fill Calculator (NEC 40% Rule) and add your input
Type your numbers or text, add your file, or pick the options you need. Nothing is uploaded: everything stays in your browser.
- 2Step 2: What Conduit Fill Calculator (NEC 40% Rule) does
Check conduit fill for THHN wires and find the smallest EMT size that meets the NEC limit.
- 3Step 3: Read the result and compare
The result appears at once. Change one value to see how the answer moves, then keep the figure that fits your case.
- 4Step 4: Copy or save it
Copy the result or download it. For an important decision, confirm it with the official source or an adviser.
About this tool
Enter how many THHN conductors of each size you will pull. The calculator adds their cross-sectional area, applies the NEC fill limit and finds the smallest EMT conduit that stays within it.
The rule
NEC Chapter 9 Table 1 limits conduit fill to 53% of the area for one conductor, 31% for two and 40% for three or more. Fill is the total area of the conductors divided by the internal area of the conduit.
Areas used
THHN conductor areas in square inches: 14 AWG 0.0097, 12 AWG 0.0133, 10 AWG 0.0211, 8 AWG 0.0366, 6 AWG 0.0507, 4 AWG 0.0824, 2 AWG 0.1158. EMT internal areas: ½ inch 0.304, ¾ inch 0.533, 1 inch 0.864, 1¼ inch 1.496, 1½ inch 2.036, 2 inch 3.356 square inches.
Limits
This covers THHN/THWN in EMT. Other conduit types and wire insulation have different areas. Conductor derating and bend limits are not checked.
Worked example
Six 12 AWG and three 10 AWG THHN conductors have a total area of 0.1431 in². With nine conductors the limit is 40%, and ½ inch EMT allows only 0.1216 in², so ¾ inch EMT is needed at 26.8% fill.
Tips for best results
Check every box before you rely on a result, because one wrong digit changes the whole answer. Use the exact figures from your payslip, bill, certificate or contract, and keep a note of the date you calculated. Rates, thresholds and rules change from time to time, so for tax, fees and legal matters treat the output as an estimate and confirm with the official source named on this page. You can run as many scenarios as you like; nothing is saved or sent, and refreshing the page clears the boxes.
Quick facts
- Category: UK & US
- Works in your browser, no sign-up, no upload.
- Your input stays on your device.
- Available in English.
- Content last reviewed:
Frequently asked questions
Why 40%?
It leaves room to pull the wires and dissipate heat.
Does it apply to all conduit?
The percentages apply to all types, but the internal areas differ by type.
Do I count the ground wire?
Yes, every conductor including grounds counts.
What about nipples?
Short nipples up to 24 inches may be filled to 60%.