Fire Alarm Zone and Detector Planner (BS 5839-1)
Enter floor areas and storeys to get the number of detection zones under BS 5839-1, or a room's length and width to estimate how many point smoke or heat detectors it needs.
Εκτελείται στο πρόγραμμα περιήγησής σας. Τα αρχεία σας δεν φεύγουν ποτέ από τη συσκευή. Δείτε πώς να το ελέγξετε
…
Πώς γίνεται
- 1Choose zones or room
Mode.
- 2Enter floor areas
And storeys.
- 3Check the search distance
Under 60 m.
- 4Enter room size
For detector counts.
- 5Choose detector type
Smoke or heat.
Σχετικά με αυτό το εργαλείο
Fire alarm systems divide a building into detection zones so that responders can find a fire quickly from the control panel. BS 5839-1, the UK code of practice for non-domestic premises, limits each zone to 2,000 m² of floor area and the search distance within a zone to 60 m, and normally confines a zone to one storey unless the whole building is no larger than 300 m². Within each room, point detectors must cover every part of the ceiling: no point may be more than 7.5 m horizontally from a smoke detector or 5.3 m from a heat detector. This calculator gives the minimum number of zones per storey and in total, and estimates detector numbers for a rectangular room on a square grid.
Who this is for
Fire alarm designers and installers, building services engineers, fire risk assessors, facility managers and students.
Zoning rules (BS 5839-1)
- Floor area of a zone: no more than 2,000 m². - Search distance (to see the location of a fire within the zone): no more than 60 m. - A zone should not cover more than one storey, unless the total floor area of the building is 300 m² or less. - Stairwells, lift shafts and similar vertical structures are usually separate zones. - Where addressable systems identify each device, zones still help responders plan.
Detector coverage
- Smoke detectors: every point within 7.5 m horizontally. - Heat detectors: within 5.3 m. On a square grid, the maximum spacing is r·√2: 10.6 m for smoke, 7.5 m for heat, each detector covering about 112 m² and 56 m² respectively. Corridors under 2 m wide allow longer spacing along the corridor. Sloping ceilings, beams, voids and ceiling height (smoke up to about 10.5 m, heat up to 9 m for typical grades) change these rules.
Worked example
A three-storey building of 4,500 m² per floor needs at least three zones per floor, nine in total. A 20 × 15 m room needs four smoke detectors on a 10.6 m grid, one per 75 m².
System categories
BS 5839-1 categories range from M (manual call points only) through L1-L5 (life protection) to P1-P2 (property protection). The category decides where detectors are required.
Example uses
A designer splits a large warehouse floor into zones. A fire risk assessor checks whether an existing panel's zones meet BS 5839-1. An installer estimates detector numbers for a quote.
Manual call points
Call points are placed on exits to storeys and to open air, so that nobody walks more than 45 m to one (25 m in some higher-risk areas).
Limits
Simplified rectangular layouts; obstructions, ceiling shape and specific product data change spacing. Designs must be checked by a competent person. This is not professional fire safety advice.
Λυμένο παράδειγμα
4,500 m² per floor, 3 storeys: at least 9 zones; a 20 × 15 m room needs 4 smoke detectors.
Με μια ματιά
- Κατηγορία: Μηχανική & κατασκευές
- Εκτελείται στο πρόγραμμα περιήγησης, χωρίς εγγραφή, χωρίς μεταφόρτωση.
- Τα στοιχεία που εισάγετε μένουν στη συσκευή σας.
- Διαθέσιμο στα αγγλικά.
- Τελευταία αναθεώρηση περιεχομένου:
- Επίσημη πηγή: BS 5839-1:2017 fire detection and alarm systems: zone area up to 2,000 m², search distance up to 60 m, single zone for buildings up to 300 m²; point detector coverage radius 7.5 m (smoke) and 5.3 m (heat) under flat ceilings
Συχνές ερωτήσεις
How big can a fire alarm zone be?
No more than 2,000 m² under BS 5839-1.
What is the search distance?
The walking distance to find a fire within a zone, no more than 60 m.
Can one zone cover several floors?
Only if the whole building is 300 m² or less.
How far apart can smoke detectors be?
About 10.6 m on a square grid, so no point is over 7.5 m from a detector.
Does this replace a design?
No. It gives preliminary quantities.
Is my data stored?
No. Building data stays in this browser.